10 group mapping – Alpha Technologies AMPS80 HP User Manual
Page 67
![background image](/manuals/317354/67/background.png)
65
Doc. #: 026-069-B0 Rev F
6.3.10 Group Mapping
A matrix of buttons allows the supervisor to map (enable/disable) the inverter's assignment per group for all
of the acquired inverters in the system.
Power buttons – Green indicates an inverter is turned ON. An amber/orange/yellow color indicates the
inverter is in a recoverable error. The user can attempt to turn on the unit. The red color indicates the inverter
is in an irrecoverable error and there is nothing the user can do to turn on the unit. Black indicates an inverter
is manually OFF. Adding/removing groups (columns) may take a few seconds to incorporate the change.
Changing the radio style buttons (rows) will also take time to apply changes; for example, approximately two
seconds for one inverter and up to ten seconds for the maximum number of inverters (32).
If there are inverters mapped to a column, disabling a column is prevented and a warning message is dis-
played.
All inverters must be turned OFF to enable the AC Output Groups column buttons. The AC Output Groups of
an inverter in the ON state cannot be changed. The radio buttons for that inverter AC output group will remain
disabled until the inverter is turned OFF.
Figure 46 —
Group mapping window
Ensure phases are configured
correctly before mapping invert-
ers in the new groups and turning
them on.
"Power Buttons"
Click these buttons to switch
the inverter ON/OFF. Use with
caution.
Green = inverter is ON
Black = inverter is OFF
Amber/Red = inverter ALARM