6.4 Rectifier Features

6.4.1 Rectifier Front Panel Lights

Refer to the Cordex CXRF 48-1.8 kW manual for further details.

AC LED light

The top LED (green) is on when AC

is within valid range. AC voltage is

invalid if the AC Mains Low or AC

Mains High alarm is active. The

LED turns off when AC has failed.

DC LED light

The middle LED (green) is on when

the rectifier is delivering power to

the load. The LED will flash when

communication is lost. The LED

turns off when the rectifier is off;

e.g., when commanded via the

controller.

Figure 55 —

Cordex CXRF 48 V rectifier

Alarm (ALM) LED light

The bottom LED (red) is on continuously

in the event of an active Module Fail

alarm; if the module is unable to source

power as a result of any of the following

conditions:

• Output fuse blown

• AC Mains Input Fail

• Module fail (ramp test fail)

• High voltage (OVP) shutdown

• Thermal shutdown

• Local shutdown

• UPF fail

• No output power

• Fan fail.

The LED will flash (~2Hz) when a minor alarm is detect-

ed; if the modules output capability has been reduced

or a minor component failure is detected during the

following conditions:

• VAC meter fail

• AC foldback

• Remote equalize

• Fan fail

• Low output voltage

• High output voltage

• Current limit (programmable option)

• Power limit (programmable option)

• High temperature foldback

• Temperature sense fail

• Soft start operation

• Communications lost.

The LED remains off in the absence of an alarm. If the

unit output is not connected to a battery or parallel rec-

tifier, the LED will extinguish if no AC power is present.

AC LED light

DC LED light

Alarm LED light