5.1 Input/Output Cabling Overview

Connection points are accessed from the top of the unit. A protective panel partitions the AC and DC con-
nections

.

DC2

DC3

DC4

Protective panel between

AC & DC connections

DC connections

AC connections

AC input ground

AC output ground

Frame ground

5.1.1 Wiring Gauge

The required gauge of the AC input, DC+/DC- input and AC output cabling is determined by the current rat-

ing, circuit breaker rating, typical ambient temperatures and the applicable local electrical codes. Typically

the AC input and standard AC output is 6 wires (L1, L2, and L3, N, N, G) up to 350 kcmil THHW or RW90

type cable that connects to the AMPS80 HP system with trade size up to 2.5" conduit.

5.1.2 Grounding

Refer to Figure 20 for connection points for frame ground, AC input ground and AC output ground.

Ground

bus

DC1

Figure 20 —

Top view of AMPS80 showing AC and DC connection partitions