ELECTRICAL INSTALLATION & WIRING

Page

3-3

3

LS300 User’s Guide

Figure 3-2 LSU300 Intrinsically Safe Wiring w/ No-Strip Wire Splice at

Weatherproof Junction Box

Wire Intrinsically Safe LSU300 transducers only to
TS-LS300 version consoles in conduit apart from non-intrinsically safe
wiring. DO NOT run intrinsically safe wiring in the same conduit with non-
intrinsically safe wiring.

NOTE

Beldon #9363-22 AWG,
#9364-20 AWG, #9365-18AWG
or equivalent recommended.
Max Cable length is 500 feet.

LS300 Auto-Learn
Line Leak Detector
Console (CU)

3 CONDUCTOR
CABLE 6FT
(1.83 meters)
Supplied

Syphon

Plug

Tank

Plug

Follow all federal, state, and local
laws & codes governing the
installation of this product & the
entire system.

Maximum safe area voltage must
not be greater than 250 Vrms.

TO SPLICE:
INSERT
UNSTRIPPED
WIRES & USE
SLIP-JOINT
PLIERS TO SEAT BLACK PIECE

BLK

SHIELD

WHT

BLK

SH

IE

LD

WH

T

RED

Annunciator States/Conditions

Auto-Learn
Line Leak Detector

4

3

2

1

TS-LS300

TEST

/

RESET

TEST

PASSED

ALARM

FAILED

Annunciator Legend

HI

PUMP ON

LO

RE

D

ALARM

FAILED

ALARM

FAILED

ALARM

FAILED

INTELLIGENT CONTROLS

PRESSURE

PRESSURE

PRESSURE

PRESSURE

HI

PUMP ON

HI

PUMP ON

HI

PUMP ON

TEST

/

RESET

TEST

/

RESET

POWER

TEST

/

RESET

LO

LO

TEST

PASSED

TEST

PASSED

LO

TEST

PASSED

R

No-Strip Electrical
Connectors inside

Weather

Proof J-Box

(Junction Box)

5 FT (1.53 meters)

MAX from LSU300

Transducer

LSU300

Pressure

Transducer

STP

HOUSING

Coupling

EYS (Epoxy Y Seal)

Fitting TYP

3/4 inch NPT Conduit

and Fittings
(DN20NPT)

for I.S. Wiring Only

- Typical -

For CE
compliance the
cables from the
console to the
LSU300
Transducer must
be installed in
metal conduit,
rigid or flexible

NOTE