Clearing Alarms

Clearing a console of alarms is important because, depending on how the T5 FMS console has been set up, alarms can: 

disable channels, start an annunciator, or stop an SCM test under way.
Administrator privileges will be necessary to clear SCM alarms on the T5 FMS console. For instructions on how to obtain 

an Administrator access level, please refer to the T5 FMS Programming Guide (p/n 000-2142).
1.  Identify the alarm on the SCM Alarms screen.
2.  Diagnose the condition using information found in the Alarms chapter of this guide.
3.  Follow the troubleshooting steps in the previous section of this chapter to correct the issues indicated by the alarms.
4.  Navigate to the SCM Control screen.
5.  Select 

Reset Alarms on the Control screen. 

6.  If Auto-Enable on Reset is chosen in the SCM Setup, then the containment will enable automatically. Otherwise, select 

Enable/Disable on the Control screen.

If the condition still exists, the alarm can take up to several hours to reappear after the containment is enabled.