4-20mA Input Module

SCCM Vacuum Sensors use a single 4-20mA channel per sensor to accept an incoming signal that allows the console to 

monitor secondary containment vacuum levels.

Parameter

Parameter Value

Channels

The total number of channels used for SCM, LLD, or other analog devices connected to the module.

Enabled

Set to Yes.

Name

Should be a specific device or location where the SCCM Vacuum Sensor is located.

Service Type

Indicates the type of device sending the input to the console. Choose Secondary Containment Monitor to indicate 

that the device is a SCCM 4-20mA Vacuum Sensor.

Example: 4-20mA Input Module SCM Setup

Group Name

Parameter Name

Parameter Value

4-20mA Input Modules

Module ‘#’

Channels ‘#’

Channel ‘#’

Name Regular SCCM Vacuum Sensor

Enabled Yes

Service Type Secondary Containment Monitor

Channel ‘#’

Name Premium SCCM Vacuum Sensor

Enabled Yes

Service Type Secondary Containment Monitor

Channel ‘#’

Name Diesel SCCM Vacuum Sensor

Enabled Yes

Service Type Secondary Containment Monitor

Relay Module

The Relay Module contains eight separate relays (called Relay Channels). A channel is used to open and close an 

individual SCCM solenoid. For SCM, the solenoid relay channel is controlled by an input from the 4-20mA Input Module 

(the SCCM Vacuum Sensor channel).

Parameter

Parameter Value

Channels

The total number of channels used for any equipment connected to the module.

Enabled

Set to Yes.

Input Channel

Select the 4-20mA Input Module channel connected to the SCCM vacuum sensor on the same SCCM as 

the solenoid being programmed.

Input Type

Select the 4-20mA Input Module that contains the SCCM vacuum sensor on the same SCCM as the 

solenoid being programmed.

Logic

Set to OR logic.

Name

Should be a specific device or location of the SCCM Solenoid connected to the relay.

Number of Inputs

Set to 1. 

Physically Wired As

Select Normally Open to indicate which contacts the solenoid is wired to.

Polarity

Set to Normal.

Type

Select Solenoid for type identify the type of device connected to the relay is a SCCM solenoid.