Secondary Containment Monitoring Application

Programming the SCM application sets the parameters for SCM and enables it to monitor a set number of channels. Each 

containment area or group must be programmed separately on the T5 FMS console.

Parameter

Parameter Value

Auto-Enable on Reset

A feature that allows the Containment area to enable itself after an alarm condition is cleared, or 

when the system is powered on or reset.

Enabled

Set to Yes.

Name

Should be a specific location or product type of the containment area.

Number of Containments

The number of SCCMs connected to the console.

Pump Shutdown on Alarm

If set to Yes, provides positive pump shutdown when the containment area is in alarm.

Submersible Pump Channel

Maps the containment area to the specific pump control output channel.

Submersible Pump Module

Maps the containment area to a specific pump to provide pump on/off.

Transducer

Maps the containment area to the SCM Vacuum Sensor as specified by the 4-20mA Input Module 

channel assignments.

Example: SCM Application Setup

Group Name

Parameter Name

Parameter Value

Secondary Containment Monitor

Number of Containments 3

Containment 1

Name Unleaded Line Containment

Enabled Yes

Pump Shutdown on Alarm Yes

Auto-enable on Reset Yes

Submersible Pump Module Relay Module (or Power Supply for TPI)

Submersible Pump Channel Unleaded Pump Control

Transducer Unleaded SCCM Vacuum Sensor

Containment 2

Name Premium Line Containment

Enabled Yes

Pump Shutdown on Alarm Yes

Auto-enable on Reset Yes

Submersible Pump Module Relay Module (or Power Supply for TPI)

Submersible Pump Channel Premium Pump Control

Transducer Premium SCCM Vacuum Sensor

Containment 3

Name Diesel Line Containment

Enabled Yes

Pump Shutdown on Alarm Yes

Auto-enable on Reset Yes

Submersible Pump Module Relay Module (or Power Supply for TPI)

Submersible Pump Channel Diesel Pump Control

Transducer Diesel SCCM Vacuum Sensor