Scm setup (console programming), Ac input module – Franklin Fueling Systems TS-550/TS-5000 consoles Secondary Containment Monitoring User Manual

Page 10

background image

7

SCM Setup (Console Programming)

The following instructions will guide you through SCM programming only. Administrator privileges will be necessary to 

program the SCM application for the T5 FMS console. For instructions on FMS programming or on how to obtain an 

Administrator access level, please refer to the T5 FMS Programming Guide (p/n 000-2142).
Access the T5 FMS console (via the LCD or Tank Sentinel Anyware - TSA) and navigate to the Setup Menu. Once at the 

Setup Menu, go to each of the following sections and adjust SCM parameters accordingly. You will be prompted to enter 

the Administrator access level when it is required.
Note:  Sites setups vary depending on products used and other equipment installed. Setup information in the sections of 

this chapter depict a typical site and are meant as examples only.

AC Input Module

The AC Input Module can accept incoming dispenser hook control signals. Hook signals are used to activate the STP via 

the relay channel connected to the pump controllers. Control signals from the dispenser tell the console which product is 

requested by the dispenser, then control signals activate the appropriate STP. To perform tests accordingly, SCM needs to 

know when pumps/dispensers are being used by other applications.

Parameter

Parameter Value

Active High

If set to Yes, a high signal level will activate the channel and a low signal will deactivate the channel. If 

set to No, then the channel is inverted and will only become active when a signal is absent and inactive 

when a signal is present.

Channels

Only select the total number of inputs intended for use.

Enabled

If yes, will allow the channel to be mapped to another module. Other modules may use this signal to 

trigger an event.

Name

Should be a specific device from which the signal is originated.

Number Gasoline Hooks 

per Dispenser

The number of product hook signal inputs to the console from the dispensers.

Example: AC Input Module SCM Setup

Group Name

Parameter Name

Parameter Value

AC Input Modules

Number Gasoline Hooks per Dispenser 2

Module ‘#’

Channels ‘#’

Channel ‘#’

Name Disp 1 Unleaded Hook Signal

Enabled Yes

Active High Yes

Channel ‘#’

Name Disp 2 Unleaded Hook Signal

Enabled Yes

Active High Yes

Channel ‘#’

Name Disp 3 Unleaded Hook Signal

Enabled Yes

Active High Yes