SCM Status and Control Screens

The status of each containment channel can be viewed at any time by navigating to the SCM Status or Control screens. 

To get to the SCM Status or Control screens, go to 

SCM > Status (Summary) or SCM > Control (Containment).

SCM Status Summary Screen

When viewing the SCM Status Summary screen, remember to enable Auto Refresh. The Auto Refresh

button will 

allow the on-screen results to be automatically updated. When the results will update is dependent on the user-defined 

parameter Refresh Rate

found on the Configuration page.

Status and Alarm Indicators

Indicator

Description

Fail to Hold Vacuum

The containment will not maintain the learned level of vacuum.

Fail to Reach Vacuum

The containment has not reached the learned level of vacuum.

High Vacuum

The vacuum level of the containment has exceeded 9" Hg.

Low Vacuum

The vacuum level of the containment has dropped below 1.25" Hg.

Not Learned

The containment has not been learned.

Program Error

SCM has encountered an error.

Pump Request

SCM is attempting to cycle the pump on.

Pump Request Ignored

The pump is being used by another application.

Sensor Malfunction

SCM has detected a failure of the SCCM vacuum sensor.

Solenoid Status

Indicates whether the normally closed SCCM solenoid is open or closed.

Status

Indicates the condition of the containment.

Vacuum Level

A direct reading from the SCCM vacuum sensor.

Vacuum Unstable

The level of vacuum in the containment is not statistically sound.

For more information on alarms and troubleshooting, refer to the Alarms chapter in this manual.