Scm status and control screens, Scm status summary screen – Franklin Fueling Systems TS-550/TS-5000 consoles Secondary Containment Monitoring User Manual
Page 15
12
SCM Status and Control Screens
The status of each containment channel can be viewed at any time by navigating to the SCM Status or Control screens.
To get to the SCM Status or Control screens, go to
SCM > Status (Summary) or SCM > Control (Containment).
SCM Status Summary Screen
When viewing the SCM Status Summary screen, remember to enable Auto Refresh. The Auto Refresh
button will
allow the on-screen results to be automatically updated. When the results will update is dependent on the user-defined
parameter Refresh Rate
found on the Configuration page.
Status and Alarm Indicators
Indicator
Description
Fail to Hold Vacuum
The containment will not maintain the learned level of vacuum.
Fail to Reach Vacuum
The containment has not reached the learned level of vacuum.
High Vacuum
The vacuum level of the containment has exceeded 9" Hg.
Low Vacuum
The vacuum level of the containment has dropped below 1.25" Hg.
Not Learned
The containment has not been learned.
Program Error
SCM has encountered an error.
Pump Request
SCM is attempting to cycle the pump on.
Pump Request Ignored
The pump is being used by another application.
Sensor Malfunction
SCM has detected a failure of the SCCM vacuum sensor.
Solenoid Status
Indicates whether the normally closed SCCM solenoid is open or closed.
Status
Indicates the condition of the containment.
Vacuum Level
A direct reading from the SCCM vacuum sensor.
Vacuum Unstable
The level of vacuum in the containment is not statistically sound.
For more information on alarms and troubleshooting, refer to the Alarms chapter in this manual.