beautypg.com

Rack mounting the switcher, Ul guidelines, Mounting instructions – Extron Electronics Matrix 12800 Series User Guide User Manual

Page 18: Ul guidelines -3 mounting instructions -3, Preliminar y

background image

2-3

Matrix 12800 Switchers • Installation

PRELIMINAR

Y

Rack Mounting the Switcher

The Matrix 12800 sync, wideband video, video, and audio BMEs are rack-

mountable, 10U high, 17.5-inch wide (19-inch wide, including rack ears) metal

enclosures. The appropriate rack mounting kit is included with the switcher. Rack

mount the switcher as follows:

UL guidelines

The following Underwriters Laboratories (UL) guidelines pertain to the installation

of the Matrix 12800 switcher BME into a rack.

1

.

Elevated operating ambient temperature

— If installed in a closed or

multi-unit rack assembly, the operating ambient temperature of the rack

environment may be greater than room ambient. Therefore, consider installing

the equipment in an environment compatible with the 122 °F (+50 °C)

maximum ambient temperature (Tma) specified by Extron.

2

.

Reduced air flow

— Installation of the equipment in a rack should be such

that the amount of air flow required for safe operation of the equipment is not

compromised.

3

.

Mechanical loading

— Mounting of the equipment in the rack should be such

that a hazardous condition is not achieved due to uneven mechanical loading.

4

.

Circuit overloading

— Consideration should be given to the connection of the

equipment to the supply circuit and the effect that overloading of the circuits

might have on overcurrent protection and supply wiring. Appropriate

consideration of equipment nameplate ratings should be used when

addressing this concern.

5

.

Reliable earthing (grounding)

— Reliable earthing of rack-mounted

equipment should be maintained. Particular attention should be given to

supply connections other than direct connections to the branch circuit (e.g. use

of power strips.

Mounting instructions

1

.

Insert the switcher into the rack, align the holes in the mounting bracket with

those of the rack.

2

.

Secure the switcher to the rack using the supplied machine screws.