beautypg.com

Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 71

background image

71

Point

Num.

Descriptor

Factory Default

(SI)

Units

(SI)

Slope

(SI)

On

Text

Off

Text

R

ange

Max

V

alue

(SI)

Min

V

alue

(SI)

Point

Type

Class

Type

R

ead

Only

Par

ameter#

Bit

66

PID D TIME

0

SEC

0.01

0

16383

1000

0

1

LAO

No

2095

67

--Free P

oint

--

68

FB FUNCTION

7

1

0

255

255

0

1

LDO

No

2020

69

SETPOINT 1

0

UNIT

0.1

-1638.3

32767

1638300

1

LAO

No

2021

70

SETPOINT 2

0

UNIT

0.1

-1638.3

32767

1638300

1

LAO

No

2022

71

SETPOINT 3

0

UNIT

0.1

-1638.3

32767

1638300

1

LAO

No

2023

72

SETPOINT 4

0

UNIT

0.1

-1638.3

32767

1638300

1

LAO

No

2024

73

--Free P

oint

--

75

BUS FBK 1

0

PCT

0.01

-163.83

32767

16383

-16383

1

LAO

No

894

76

BUS FBK 2

0

PCT

0.01

-163.83

32767

16383

-16383

1

LAO

No

895

77

BUS FBK 3

0

PCT

0.01

-163.83

32767

16383

-16383

1

LAO

No

896

78

--Free P

oint

--

80

DRV ENA PUMP1

0

1

0

ENABLE

DIS

ABL

255

255

0

3

LDI

Yes

1603

2

81

DRV RD

Y

PUMP1

0

1

0

READ

Y

NO

TRD

Y

255

255

0

3

LDI

Yes

1603

1

82

DRV CTL PUMP1

0

1

0

READ

Y

NO

TRD

Y

255

255

0

3

LDI

Yes

1603

0

83

--Free P

oint

--

88

LOW SUCTION

0

1

0

ALARM

OK

32767

32767

0

3

LDI

Yes

3905

8

89

HI SYS PRES

S

0

1

0

ALARM

OK

32767

32767

0

3

LDI

Yes

3905

7

90

OK W

ARNING

0

1

0

W

ARN

OK

255

255

0

3

LDI

Yes

1603

7

91

CRNT W

ARNING

0

1

0

32767

32767

0

3

LAI

Yes

92

GEN ALARM

0

1

0

FA

UL

T

OK

255

255

0

1

LDO

Yes

3902

2

93

LA

ST F

A

UL

T

0

1

0

255

255

0

3

LAI

Yes

1530

94

RESET F

A

UL

T

0

1

0

YES

OK

255

255

0

1

LDO

No

1685

7

95

ACTIVE SETUP

0

1

0

255

255

0

3

LAI

Yes

10

96

--Free P

oint

--

99

ERROR ST

A

TUS

0

1

0

255

255

0

3

LAI

Yes