Warning, Line input (mains) connection, Wire type rating – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual
Page 15: Terminal tightening torques, Ground lug line (mains) disconnect ground bar, Exterior interior
15
Line Input (Mains) Connection
• Size wiring based upon the input current
of the drive. Recommended wire sizes are
provided on the connection drawing of the
unit.
• Local codes must be complied with for cable
sizes.
Figure 3-5. Input Power Panel with Line Disconnect
Exterior
Interior
OT 45...100 M3
Ground lug
Line (mains)
disconnect
Ground bar
L1 L2 L3
Wire Type Rating
• Use wiring corresponding to the wire
rating specification provided.
• The wire rating specification is located
on the wire rating label inside the cover
of the option panel.
Terminal Tightening Torques
• Tighten all connections to the torque
specification provided in Table 3-2.
WARNING
!
r
un
input
powEr
,
motor
wiring
and
control
wiring
in
tHrEE
sEparatE
mEtallic
conduits
or
racEways
for
HigH
frEquEncy
noisE
isolation
. f
ailurE
to
isolatE
powEr
,
motor
and
control
wiring
could
rEsult
in
lEss
tHan
optimum
drivE
and
associatEd
EquipmEnt
pErformancE
.
• Connect 3-phase AC input power wire
to terminals L1, L2, and L3 on the main
disconnect located in the input power panel
(see Figure 3-3).
• Depending on the configuration of the
equipment, input power may be connected
to a circuit breaker or input disconnect.
•
Use with Isolated Input Source. Many
utility power systems are referenced to earth
ground. Although not as common, the input
power may be an isolated source. All drives
may be used with an isolated input source
as well as with ground reference power
lines.
notE
s
EE
f
igurEs
3-12
and
3-13
for
powEr
,
motor
and
control
wiring
diagrams
.