Line Input (Mains) Connection

• Size wiring based upon the input current

of the drive. Recommended wire sizes are

provided on the connection drawing of the

unit.

• Local codes must be complied with for cable

sizes.

Figure 3-5. Input Power Panel with Line Disconnect

Exterior

Interior

OT 45...100 M3

Ground lug

Line (mains)

disconnect

Ground bar

L1 L2 L3

Wire Type Rating

• Use wiring corresponding to the wire

rating specification provided.

• The wire rating specification is located

on the wire rating label inside the cover

of the option panel.

Terminal Tightening Torques

• Tighten all connections to the torque

specification provided in Table 3-2.

WARNING

!

r

un

input

powEr

,

motor

wiring

and

control

wiring

in

tHrEE

sEparatE

mEtallic

conduits

or

racEways

for

HigH

frEquEncy

noisE

isolation

. f

ailurE

to

isolatE

powEr

,

motor

and

control

wiring

could

rEsult

in

lEss

tHan

optimum

drivE

and

associatEd

EquipmEnt

pErformancE

.

• Connect 3-phase AC input power wire

to terminals L1, L2, and L3 on the main

disconnect located in the input power panel

(see Figure 3-3).

• Depending on the configuration of the

equipment, input power may be connected

to a circuit breaker or input disconnect.

Use with Isolated Input Source. Many

utility power systems are referenced to earth

ground. Although not as common, the input

power may be an isolated source. All drives

may be used with an isolated input source

as well as with ground reference power

lines.

notE

s

EE

f

igurEs

3-12

and

3-13

for

powEr

,

motor

and

control

wiring

diagrams

.