Pump Alternation Time (Old

Par. 770)

0s

999s

0s

When not all pumps are operating,

this determines the number of hours

of pump operation before pump

alternation occurs. When the pumps

are manually alternated using the right

or left arrow keys on the Local Control

Panel, this timer is reset.

39-32

Alternation Start Delay Time 0s

999s

0s

It is often desirable to have alternation

occur at off peak times, such as at

night. To allow the system to be setup

during normal hours to alternate every

night this start delay parameter is used.

It defines the length of time before the

next alternation.

39-33

Pump Run Order

0 - Runtime Order

1 - First On First Off

2 - Sequential Order

0

2

2

The controller selects the next pump

to stage, destage or alternate. Equal

Running Hrs will cause the controller

to turn on the pump with the fewest

running hours and to trun off the piump

with the most running hours. Sequential

Order will turn on the pump to the right

of the lead pump and will turn off the

pump to the farthest left of the lead

pump regardless of running hours.

39-34

Lead Pump Number

1

4

A display of the current lead pump

number used by the controller for

sequential staging and destaging. This

is only significant if Sequenctial Order

is selected in P39-33.

39-35

“Alternate Lead Pump Now

[0] - No

[1] - yes”

0

1

0

Selecting [1] Yes will cause the

immediate alternation of the lead pump.

After alternation the parameter returnes

to [0] No.

39-39

Time Until Daily Alternation

A display of the time remaining before

the next alternation will occur.

39-4* Alms/

Sensor

Fault

39-40

AFD Fail Proof Timer (Old

Par. 771)

0s

200s

10s

After the controller commands a pump

to run, it will check for confirmation that

the pump is running. If the controller

does not receive run confirmation

before the timer set in this parameter

expires, it will stage on a different pump

and display WARINIG, DRIVE FAILED.

39-41

Pump Fail Proof Timer (Old

Par. 771)

0s

200s

10s

After the controller commands a pump

to run, it will check for confirmation that

the pump is running. If the controller

does not receive run confirmation

before the timer set in this parameter

expires, it will stage on a different pump

and display WARINIG, PUMP FAILED.

Table 6-2. Parameter 39-** Group, Detailed Description (continued)