Installation of 70X Series Drives and

Pumps

A 70X configuration consists of one variable speed

pump (lead pump) connected to the 70X controller,

and from 1 to 3 constant speed pumps connected

to mains through a contactor controlled by the 70X

controller. (See Figure 3-15.)

The 70X controller monitors system pressure and

stages on and off constant speed pumps as needed

to maintain system pressure. Parameter 27-20,

Normal Operating Range % is used to define the

acceptable deviation from the setpoint before staging

or destaging takes place. This parameter is defined

as a % of parameter 3-03, Maximum Reference.

(See Figure 3-16 for customer connection schematic

diagram.)

Staging:

When the system demand increases the 70X

controller will increase the speed of the lead pump

until it reaches its maximum speed. If the system

demand continues to increase, it will no longer be able

to maintain the desired system pressure. Once the

pressure drops below the Normal Operating Range for

the time set in parameter 39-11, Stage Proof Timer,

the controller will stage on a constant speed pump

and ramp the lead pump to its minimum speed.

De-Staging:

When system demand decreases, the 70X controller

will decrease the speed on the lead pump until it

reaches its minimum speed. If the system demand

continues to decrease, the pressure will exceed the

Normal Operating Range. If this continues for the time

set in parameter 39-14, De-Stage Proof Timer, the

controller will destage a constant speed pump and

ramp the lead pump to maximum speed.

Alternation:

Since timed alternation only applies to changing the

lead pump, it is not part of a 70X system which has

only one lead pump. It is possible however to manually

alternate constant speed pumps using the right and

left arrows on the LCP.

Pump Running Order:

Parameter 39-33, Pump Running Order can be used

to determine the sequence with which constant speed

pumps are staged on and off.

AFD Failure and Fixed Speed Only mode:

Parameter 39-40, AFD Fail Proof Timer is active

in the 70X configuration. If the AFD fails, the 70X

system will switch to Fixed Speed Only mode.

In this mode, the controller will stage on and off

constant speed pumps if the system pressure

deviates from the setpoint more than parameter

27-22, Fixed Speed Only Operating Range. Setting

27-22 to zero disables this mode.

Pump Failures:

The DP switch inputs can be used in the 70X

configuration. If a failure is detected in the lead pump,

the controller will switch to Fixed Speed Only mode as

described above. If a failure is detected in a constant

speed pump, the controller will alternate to a different

constant speed pump and mark the pump as failed.

Zone Failure Detection:

All of the normal Zone Failure detections can be used

in the 70X configuration. The loss of a single sensor will

disable that sensor. The loss of all sensors will pump

the system into jog mode. 70X jog mode will run the

designated number of pumps at full speed by default.