beautypg.com

Typical bypass operation, Overload protection – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 7

background image

7

Figure 1-3. Basic 3-contactor Bypass Functions

Typical Bypass Operation

With contactors M1 and M2 closed and contactor M3

open (see Figure 1-3), the pump is controlled by the

drive. Opening contactor M2 removes power to the

pump but allows the controller to remain powered.

This is the test mode and only available in the three-

contactor configuration shown. With contactors M1

and M2 open and contactor M3 closed, the pump

runs in bypass from the line input. For a two-contactor

configuration, M1 is absent. In this case, contactors

M2 and M3 control the options for running in drive or

bypass mode. The figure illustrates a drive disconnect

and fuses.

Overload Protection.

This thermally activated device provides mechanical

overload protection for the pump(s) while in bypass

operation. It measures motor current and is factory set

to the full load amps (FLA) of the pump. A 1.2 x FLA

service factor is built-in and maintained. Should the

motor current increase above that value, the overload

will calculate the level of increase to activate timing

for the trip function. The higher the current draw, the

quicker the trip response. The overload provides

Class 20 motor protection.