Warning, Drive power up, Start up procedure – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual
Page 30
30
In the following procedures, changing the equipment
between drive mode and bypass mode is required.
Be familiar with the operation of these devices in both
modes prior to start up.
Drive Power Up
E
quipmEnt
H
azard
!
d
rivE
and
option
panEls
contain
dangErous
voltagEs
wHEn
connEctEd
to
linE
voltagE
. i
nstallation
,
start
-
up
and
maintEnancE
sHould
bE
pErformEd
only
by
qualifiEd
pErsonnEl
. f
ailurE
to
pErform
installation
,
start
-
up
and
maintEnancE
by
qualifiEd
pErsonnEl
only
could
rEsult
in
dEatH
or
sErious
injury
.
1. Perform pre-start up procedure.
2. Ensure that all operator devices are in OFF
position. Panel door(s) closed.
3. Keep main disconnect switch in OFF
position. Apply voltage to unit. DO NOT
operate drive or bypass at this time.
4. Confirm input line voltage is balanced within
3%. If not, correct input voltage imbalance
before proceeding. Repeat procedure after
voltage correction, when applicable.
5. Identify master drive in multi-unit
configurations.
6. Confirm wiring matches installation diagram
supplied with unit.
7. Ensure sensor wiring matches installation
application.
8. Turn main panel disconnect into ON
position.
9. Turn main disconnect on Master drive to ON
position.
10. Turn main disconnect on Follower drive(s) to
ON position.
Start Up Procedure
WARNING
!