Grounding (Earthing)

WARNING

!

g

rounding

H

azard

!

f

or

opErator

safEty

,

it

is

important

to

ground

drivE

and

option

panEl

propErly

. f

ailurE

to

ground

drivE

and

option

panEl

propErly

could

rEsult

in

dEatH

or

sErious

injury

.

n

otE

i

t

is

tHE

rEsponsibility

of

tHE

usEr

or

cErtifiEd

ElEctrical

installEr

to

EnsurE

corrEct

grounding

(

EartHing

)

of

tHE

EquipmEnt

in

accordancE

witH

national

and

local

ElEctrical

codEs

and

standards

.

• Follow all local and national codes for proper

electrical equipment grounding (earthing).

• Proper protective grounding of the

equipment must be established. Ground

currents are higher than 3 mA.

• A dedicated ground wire is required.

• Connect the ground wire directly to a reliable

earth ground. Grounding studs are provided

on the back plate of the option panel for

grounding.

• Do not use conduit connected to the option

panel as a replacement for a ground wire.

• Do not ground one panel to another in a

“daisy chain” fashion. Each panel must have

a dedicated ground connection.

• A high strand count ground wire is preferred

for dissipating high frequency electrical

noise.

• Keep the ground wire connections as short

as possible.

notE

s

EE

f

igurEs

3-12

and

3-13

for

powEr

,

motor

and

control

wiring

diagrams

.