Set-up: Adjustment with PC

Measuring environment

• Choose “

Measuring environment“.

• Click to “

Measuring range“.

The window “

Measuring range limitation“ is

opened.

• Adjust in the window “

Measuring range

limitation“ the range in which you want to

measure. In general the measuring range
corresponds to the vessel height.

• Click to “

Save“.

• Choose in the window “

Measuring environ-

ment“ the button “Measuring conditions“.

• Adjust in the window “

Measuring conditions“

the appropriate option of your measured

product and confirm with “

OK“.

• Finally chose in the window “

Measuring

environment“ the button “Measured value

correction“.

In the window “

Echo curve“ now the echo

profile of your vessel and probable strong

false echoes are displayed. Use this indication

to improve if necessary the installation position

of your sensor and to remove or reduce prob-

able false echo sources.

• Quit the window “

Echo curve“ by clicking to

Quit“.

In the window “

Measured value correction“ the

echoes detected by the radar sensor are

displayed.

• Choose out of the detected echoes, the

echo corresponding to your measuring
distance.

• Quit this menu by entering or choosing your

measuring distance to the measured prod-

uct with “

OK“.

• Quit the window “

Measuring environment“

by clicking to “

Quit“.

You are now again in the menu “

Sensor optimi-

zation“.

Echo curve

In the menu “

Echo curve“ the echo profile of

your measurement is displayed.

• Hence click to “

Echo curve“.