VEGAPULS 64 and 81

51

5.4 Connection diagram of

VEGAPULS 81 series

Loosen the six hexagon socket screws on the

upper side of the sensor and remover the

cover of the terminal box. On the upper inner

side of the terminal box cover there is a bent

pin. Insert this pin in the terminal box cover
into the mean upper hole of the open terminal

box. hence the terminal box cover is kept

carefully during the connection work.

Connect the screen of the sensor cable with
an earth conductor of the power supply (e.g.

supply with 90 … 250 V AC) to the screen and

earth terminal in the terminal box. Connect

then the system earth (foundation or plate

earth) with the outer earth connection terminal
on the upper back side of the yellow sensor

housing or on the back of the flange.

Electrical connection

5 6 7 8 9 10

+5V

SCL GND I +

I -

U +

U -

I +

I -

1 2 3 4

SDA

Terminal board with

intrinsically safe circuits
(EEx ia)

Terminal board with
circuits in increased

safety (EEx e)

Cable entries
1 … 4 M20 x 1,5 (cable

diameter 5 … 9 mm)

Note:

The cable diameter of the connection cables

must be min. 5 mm ø and max. 9 mm ø.

Otherwise the seal effect of the cable entries
will not be ensured.

Open terminal box of VEGAPULS 81 - total view

Earth termi-

nal

Note:

Carry out screening only on one sensor end. Screen terminal
and earth terminal are electrically connected.

Screen and earth

terminal

Screen and earth

terminal or earth

conductor