VEGAPULS 64 and 81

11

Measuring system with one VEGAPULS 81 sensor (compact instru-
ment type D or E)

• Analogue, standardized 0 … 20 mA-current signal as signal output. For adjustment, a digital

adjustment signal is superimposed to the 0 … 20 mA-signal output.

• Approved in Ex Zone 0. Supply in EEx e (increased safety); output signal in EEx i (intrinsically

safe) or EEx e (increased safety).

• Adjustment and parameter adjustment via PC and the adjustment program VVO. For adjust-

ment the PC is connected via the adapter VEGACONNECT with a two-wire line to the
0 … 20 mA-signal line.

• Optionally an external digital/analogue indication. The indication can be separated from the

sensor in Ex zone 0 up to 25 m.

• The max. permissible resistance (load) of the 0 … 20 mA-signal output is 500

.

In case the input resistors of the processing systems connected to the 0 … 20 mA-signal output

are less than 100

, a resistor of more than 100

must be switched in front of the Processing

system for the adjustment period.

The digital adjustment signal is short-circuited or damped such via too small input resistors that
the digital communication with the PC would no more be ensured.

If the 0 … 20 mA-signal output is operated without resistor (load), adjustment is also not possi-

ble. Load the 0 … 20 mA-signal output during adjustment with a load resistor of 100

to 500

.

4

2

2

+

0 … 20 mA signal

output and super-

imposed digital
adjustment signal

Resistor

100

VEGACONNECT

PC with adjustment software
VEGA Visual Operating

VEGAPULS 81 F

with integral
processing

Ex-area

Non-Ex-area

EEx e or
EEx i

EEx e

EEx i

Types and versions: Configuration of measuring systems

EEx i

Zone 1

Zone 0