beautypg.com

VEGA VEGAPULS 81 User Manual

Page 13

background image

VEGAPULS 64 and 81

13

Types and versions: Configuration of measuring systems

Measuring system with 1 … 5 VEGAPULS 64 sensors per two-wire line
on the processing system VEGALOG 571

• Digital output signal; signal processing in the processing system.

• Up to five sensors on one two-wire line, 15 sensors (three groups with 5 sensors each) on one

input card. The two-wire line transmits the power supply, the digital output signal as well as the

superimposed adjustment signal.

• Adjustment and parameter adjustment via a PC and the adjustment program VVO. The PC is

connected via a RS 232-cable to the processing system. In addition the PC can be directly

connected to the sensor or the signal line via the adapter VEGACONNECT.

• Optionally an external digital/analogue indication. The indication can be separated from the

sensor up to 25 m.

• The max. permissible resistor of the two-wire line is 15

per wire or max. 1000 m cable length

between sensor and signal conditioning instrument.

VEGALOG

571 CPU

VEGALOG

571 EV

2

2

2

2

2

2

2

CPU

Current outputs
Voltage outputs
Relay outputs
Transistor outputs
Fail safe outputs
Indication outputs
Digital connectability
Connection to all BUS-

systems

Outputs (see also Product Information

“Processing system VEGALOG 571“)

Processing system VEGALOG

571 with input cards in 19“-

rack, up to 15 sensors (3 x 5)
per card

VEGACONNECT

VEGAPULS 64 with digital
signal output, up to 5 sensors

on one two-wire line

PC with adjustment software
VEGA Visual Operating

Screened cable for strong electromag-
netic interferences