Sequence of Operation

The following parameters must be programmed:

“SPACE TEMP TRENDING ALARM TEMP”- must
be programmed under SYSTEM OPTIONS tab of the
Simplicity PC software package.

“SPACE TEMP TRENDING ALARM TIME”- must
be programmed under SYSTEM OPTIONS tab of the
Simplicity PC software package.

Sequence of Operation

To enable this feature “SPACE TEMP TREND-

ING ALARM TEMP” must be set at other then
zero.

Set

“SPACE TEMP TRENDING ALARM TEMP”

to the number of degrees above or below the
space temperature that you want temperature
trending to begin. The range is 1.0° F to 25.0° F
in 1.0° F increments.

To enable this feature “SPACE TEMP TREND-

ING ALARM TIME” must be set at other then
zero.

Set

SPACE TEMP TRENDING ALARM TIME”

to the amount of time the space temperature must
be trending above or below the “SPACE TEMP
TRENDING ALARM TEMP”
before a Space
Temperature Alarm will be initiated. The range
is 1 to 120 minutes in 1 minute increments.

The unit must have been in a given operating

mode for 10 minutes before trending will be-
gin.

Every time the trend moves towards the space

temperature set point the “SPACE TEMP
TRENDING ALARM TIME”
will reset to zero

When the temperature is above or below the

“SPACE TEMP TRENDING ALARM TEMP”
and the trend continues to be away from the space
temperature and the “SPACE TEMP TRENDING
ALARM TIME”
has expired, the Simplicity Elite
control will declare a “SPACE TEMPERATURE”
Alarm. The Simplicity Elite control will fl ash an
Alarm Code 41.

The Simplicity Elite control will continue normal

operation while in this fault mode.

The Simplicity Elite control will continue to

show the fault until the space temperature is less
then the “SPACE TEMP TRENDING ALARM
TEMP”.

SAT ALARM FOR HEATING

When this feature is turned on, the Simplicity Elite
control monitors the supply air temperature in the
heating mode and will generate an alarm if the supply air
temperature goes below the set point, and if conditions
are met, modifi es the amount of ventilation air to keep
the supply air temperature above this set point when all
the heating stages are energized. This feature can only
be used on unit operating in the VAV mode.

In order to use this feature the following parameter must
be programmed:

“SUPPLY AIR TEMP ALARM SETPOINT FOR
HEATING”
– must be set under the HEATING SETUP
tab of the Simplicity PC software package.

If “SUPPLY AIR TEMP ALARM SETPOINT

FOR HEATING” is set to zero this feature is dis-
abled. If not set to zero, then the setting becomes
the alarm set point.

Set “SUPPLY AIR TEMP ALARM SETPOINT

FOR HEATING” to the temperature you want
to use for the Alarm set point. The range is 1.0°
F to 120.0° F in 1.0° F increments.

Sequence of Operation

Supply Air Temp Alarm Setpoint for Heating”
Alarm

The control will initiate a “SUPPLY AIR TEMP

ALARM FOR HEATING” and fl ash an Alarm
Code 39 if the following conditions are met:

– All the stages of heating have been on for 10

or more minutes.

– The supply air temperature is 20 degrees

below the “SUPPLY AIR TEMP ALARM
SETPOINT FOR HEATING”
set point for 10
minutes.

– The outdoor air is not 20.0° F or more cooler

then the “SUPPLY AIR TEMP ALARM
SETPOINT FOR HEATING”
set point.

– The outdoor air damper is not open more than

20%

In order to reset the above Alarm power to the

unit must be cycled on and off.