York ECO2 YPAL 050 User Manual

Page 103

background image

103

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

6

ADDRESS

NUMBER

DESCRIPTION

UNITS OF ADJUSTMENT

RANGE OF

ADJUSTMENT

CURRENT

SETTING

72/73/74/

75/76

ALARM ARRAY

DATA - 5 CHARACTERS

0 - 255

0

77

VAV / CV SELECTION

READ ONLY FLAG

CV = 0

VAV = 1

0

78

HOT GAS REHEAT

PARAMETER BIT

0 = OFF, 1 = ON

OFF

79

HOT GAS PRESENT ON COMPRESSOR # 1

PARAMETER BIT

0 = OFF, 1 = ON

OFF

80

COMPRESSORS AVAILABLE FOR COOLING

PARAMETER BIT

2 - 4

2

81

STAGES OF HEAT AVAILABLE

PARAMETER BIT

0 - 3

0 = DISABLED

2

82

DUCT STATIC READING

PRESSURE - INCHES OF

H2O

0.000 - 5.000

0000

83

BUILDING STATIC PRESSURE

PRESSURE - INCHES OF

H2O

0.000 - 5.000

0000

84

LOW AMBIENT KIT INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

85

BUILDING STATIC PRESSURE SENSOR INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

86

ERV INSTALLED

PARAMETER BIT

0 = OFF, 1 = ON

OFF

87

ERV UNOCCUPIED FAN ENABLE

PARAMETER BIT

0 = OFF, 1 = ON

OFF

88

DUCT STATIC SHUTDOWN SETPOINT

PRESSURE - INCHES OF

H2O

0.000 - 5.000

4.500

TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)