York ECO2 YPAL 050 User Manual

Page 137

background image

137

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

6

Continued on next page

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

ADDRESS

(HEX)

ADDRESS

(DEC)

BIT

INITIAL/

DEFAULT

VALUE

(HEX)

MIN

VALUE

MAX

VALUE

DESCRIPTION

A4 H

164 H

-

0

255

SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,

HIGH BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)

A4 L

164 L

-

0

255

SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,

LOW BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)

A5 L

165 L

3

0

5

SPACE SENSOR OFFSET RANGE (DEGREES)

A6 L

166 L

-

0

100

RETURN AIR HUMIDITY (%)

A7 L

167 L

-

0

100

OUTSIDE AIR HUMIDITY (%)

A8 H

168 H

-

0

255

DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, HIGH BYTE)

A8 L

168 L

-

0

255

DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, LOW BYTE)

A9 H

169 H

-

0

255

BUILDING PRESSURE VALUE (0.001” WC, HIGH BYTE, 0 = -0.250”

WC, MAX = 0.250” WC)

A9 L

169 L

-

0

255

BUILDING PRESSURE VALUE (0.001” WC, LOW BYTE, 0 = -0.250”

WC, MAX = 0.250” WC)

AA H

170 H

-

0

255

DUCT PRESSURE VALUE (0.01” WC, HIGH BYTE, 0 = 0.00” WC,

MAX = 5.00” WC)

AA L

170 L

-

0

255

DUCT PRESSURE VALUE (0.01” WC, LOW BYTE, 0 = 0.00” WC, MAX

= 5.00” WC)

AB H

171 H

0

0

200

REMOTE CONTROL INPUT VALUE (0.05 VDC COUNTS FOR

COOLING SAT SETPOINT SCALING)

AB L

171 L

40

0

200

DEMAND VENTILATION SETPOINT (25 PPM INCREMENTS,

MAXIMUM 5000 PPM)

AC L

172 L

80

0

200

AIR QUALITY (DV) SENSOR RANGE (25 PPM INCREMENTS,

MAXIMUM 5000 PPM)

AD L

173 L

60

0

240

UNOCCUPIED OVERRIDE TIME PERIOD (MINUTES)

AE H

174 H

45

0

100

OUTDOOR AIR TEMPERATURE COOLING LOCKOUT

TEMPERATURE (DEGREES F, 0 = DISABLED)

AE L

174 L

75

0

100

OUTDOOR AIR TEMPERATURE HEATING LOCKOUT

TEMPERATURE (DEGREES F, 0 = DISABLED)

AF H

175 H

50

40

65

SAT COOLING LIMIT SETPOINT (DEGREES F)

AF L

175 L

135

100

180

SAT HEATING LIMIT SETPOINT (DEGREES F)

B0 H

176 H

120

80

180

HYDRONIC HEATING STAGE #1 SUPPLY AIR SETPOINT (DEGREES

F)

B0 L

176 L

150

80

180

HYDRONIC HEATING STAGE #2 SUPPLY AIR SETPOINT (DEGREES

F)

B1 H

177 H

80

60

85

COMFORT VENTILATION UPPER SETPOINT (DEGREES F)

B1 L

177 L

70

60

85

COMFORT VENTILATION LOWER SETPOINT (DEGREES F)

B2 H

178 H

60

40

70

VAV COOLING SUPPLY AIR TEMPERATURE: UPPER SETPOINT

(DEGREES F)

B2 L

178 L

55

40

70

VAV COOLING SUPPLY AIR TEMPERATURE: LOWER SETPOINT

(DEGREES F)

B3 H

179 H

72

40

85

VAV COOLING SUPPLY AIR TEMPERATURE: RESET SETPOINT

(DEGREES F)

B3 L

179 L

68

40

85

VAV OCCUPIED HEATING SETPOINT (DEGREES F)