TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

ADDRESS

(HEX)

ADDRESS

(DEC)

BIT

INITIAL/

DEFAULT

VALUE

(HEX)

MIN

VALUE

MAX

VALUE

DESCRIPTION

0

BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 2 STAGES OF

COMPRESSION; 0,1 = 3 STAGES; 1,0 = 4 STAGES; 1,1 = 4

STAGES

1

2

1 = SAT LIMIT FOR COOLING ENABLED

3

1 = SAT LIMIT FOR HEATING ENABLED

4

1 = HYDRONIC HEATING ENABLED

5

1 = HYDRONIC HEAT ACTUATOR VALVE REVERSE ACTING

6

1 = REMOTE CONTROL INPUT ENABLED FOR THIRD PARTY BAS

7

1 = HOT GAS REHEAT ENABLED

1A L

26 L

NA

4

-

-

OPTION BYTE #3

0

1 = VAV OCCUPIED HEATING ENABLED

1

NA

2

1 = ECONOMIZER PRESENT

3

1 = OUTSIDE AIR HUMIDITY SENSOR PRESENT

4

1 = RETURN AIR HUMIDITY SENSOR PRESENT

5

1 = PRE-OCCUPANCY PURGE ENABLED

6

1 = DEMAND VENTILATION ENABLED

7

1 = BUILDING PRESSURE SENSOR INSTALLED

1B H

27 H

NA

193

-

-

OPTION BYTE #4

0

1 = POWER EXHAUST PRESENT

1

1 = MODULATING POWER EXHAUST PRESENT

2

1 = EXHAUST VFD PRESENT

3

1 = LOW AMBIENT KIT INSTALLED

4

1 = DIRTY FILTER SWITCH PRESENT

5

1 = INTELLI-START OPERATION ENABLED

6

1 = INDOOR FAN OPERATES WITH SPACE SENSOR PRESENT [CV]

7

1 = DAYLIGHT SAVINGS TIME ENABLED

1B L

27 L

NA

8

-

-

OPTION BYTE #5

0

1 = RUN TEST ENABLED

1

1 = METER OF UNOCCUPIED OVERRIDE ENABLED

2

1 = METRIC DISPLAY ENABLED

3

1 = USE THERMOSTAT OR COMMUNICATIONS FLAG FOR

OCCUPIED SIGNAL

4

1 = LEAD/LAG: EQUALIZE COMPRESSOR RUN TIME ENABLED

5

1 = HOT GAS BYPASS PRESENT ON COMPRESSOR #1

6

1 = THIRD PARTY BAS ECONOMIZER ENABLED

7

1 = MORNING WARM-UP ENABLED

1C H

28 H

NA

0

0

255

ALARM 1 - MOST RECENT ALARM.

1C L

28 L

NA

0

0

255

ALARM 2

1D H

29 H

NA

0

0

255

ALARM 3

1D L

29 L

NA

0

0

255

ALARM 4

1E H

30 H

NA

0

0

255

ALARM 5 – OLDEST STORED ALARM.