TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

ADDRESS

(HEX)

ADDRESS

(DEC)

BIT

INITIAL/

DEFAULT

VALUE

(HEX)

MIN

VALUE

MAX

VALUE

DESCRIPTION

C6 H

198 H

-

-

-

ASCD TIMER FOR COMPRESSOR #4 HIGH BYTE

C6 L

198 L

-

-

-

ASCD TIMER FOR COMPRESSOR #4 LOW BYTE (SECONDS,

COUNTS DOWN)

C7 H

199 H

0

-

-

COMPRESSOR #1 MINIMUM RUN TIMER HIGH BYTE (SECONDS,

COUNTS DOWN)

C7 L

199 L

0

-

-

COMPRESSOR #1 MINIMUM RUN TIMER LOW BYTE (SECONDS,

COUNTS DOWN)

C8 H

200 H

0

-

-

COMPRESSOR #2 MINIMUM RUN TIMER HIGH BYTE (SECONDS,

COUNTS DOWN)

C8 L

200 L

0

-

-

COMPRESSOR #2 MINIMUM RUN TIMER LOW BYTE (SECONDS,

COUNTS DOWN)

C9 H

201 H

0

-

-

COMPRESSOR #3 MINIMUM RUN TIMER HIGH BYTE (SECONDS,

COUNTS DOWN)

C9 L

201 L

0

-

-

COMPRESSOR #3 MINIMUM RUN TIMER LOW BYTE (SECONDS,

COUNTS DOWN)

CA H

202 H

0

-

-

COMPRESSOR #4 MINIMUM RUN TIMER HIGH BYTE (SECONDS,

COUNTS DOWN)

CA L

202 L

0

-

-

COMPRESSOR #4 MINIMUM RUN TIMER LOW BYTE (SECONDS,

COUNTS DOWN)

CB H

203 H

-

-

-

FAN ASCD TIMER HIGH BYTE (ALWAYS ZERO)

CB L

203 L

-

-

-

FAN ASCD TIMER LOW BYTE. (SECONDS, COUNTS DOWN)

CC H

204 H

0

-

-

FAN MINIMUM RUN TIMER (SECONDS, COUNTS DOWN)

CD H

205 H

0

-

-

FAN ON DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN)

CD L

205 L

0

-

-

FAN OFF DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN)

CE H

206 H

0

-

-

FAN ON DELAY TIMER FOR COOL (SECONDS, COUNT DOWN)

CE L

206 L

0

-

-

FAN OFF DELAY TIMER FOR COOL (SECONDS, COUNT DOWN)

CF H

207 H

0

0

255

ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, HIGH

BYTE)

CF L

207 L

0

0

255

ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, LOW

BYTE)

D4 H

212 H

-

0

100

SUPPLY FAN VFD OUTPUT STATUS, 0-100% (2 – 10 VDC)

D4 L

212 L

-

0

100

EXHAUST DAMPER OUTPUT STATUS, 0-100% (2 – 10 VDC)

D5 H

213 H

-

0

100

HOT WATER VALVE OUTPUT STATUS, 0-100% (2 – 10 VDC)

D5 L

213 L

-

0

100

HOT GAS REHEAT VALVE OUTPUT STATUS, 0-100% (2 – 10 VDC)

D6 H

214 H

-

0

100

ECONOMIZER DAMPER OUTPUT STATUS, 0-100% (2 – 10 VDC)

D7 H

215 H

NA

0

-

-

OPTION BYTE #6

0

1 = COMFORT VENTILATION FOR COOLING ENABLED

1

1 = COMFORT VENTILATION FOR HEATING ENABLED

2

1 = TEMPERATURE / HUMIDITY CONTROL ENABLED

3

1 = HOT GAS REHEAT ALTERNATE OPERATION ENABLED

4

1 = NETWORK OCCUPIED FLAG: OCC IS ON

5

NA

6

1 = DIFFERENTIAL ENTHALPY MODE ENABLED

7

NA