Electric data (continued) – York ECO2 YPAL 050 User Manual

Page 31

background image

31

2

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

TABLE 2-14 – ELECTRIC HEAT

TABLE 2-15 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS

* Cooling Only Units

KW

NOMINAL VOLTAGE

208/3/60

AMPS

230/3/60

AMPS

460/3/60

AMPS

575/3/60

AMPS

40

96

96

48

40

80

193

193

96

80

108

260

260

130

109

150

181

151

Limitations

Model Size

50

51

60

61

Minimum

Airflow at

Standard Design

Conditions.

CFM*

(min to max)

10000 -

22500

10000 -

22500

12500 -

24000

12500 -

24000

Entering Wet

Bulb Temp F°

(min/max)

57/75

57/75

57/75

57/75

Entering Dry

Bulb Temp F°

(min/max)

68/90

68/90

68/90

68/90

Ambient Temp F°

without Low

Amb option

50/120

50/120

50/120

50/120

Ambient Temp F°

with Low Amb

option

0/120

0/120

0/120

0/120

ELECTRIC DATA (CONTINUED)