York EVAPORATOR BLOWERS K2EU060 User Manual
Technical guide
®
Technical Guide
SPLIT-SYSTEM
EVAPORATOR BLOWERS
K2EU060, K4EU090, K3EU120 &
K3EU180
5 THRU 15 NOMINAL TONS
036-21300-002-A-0905
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
These completely assembled units include a well-insulated cabinet, a
DX cooling coil with copper tubes and aluminum fins, expansion
valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower
motor, an adjustable belt drive, a blower motor contactor and a small
holding charge of refrigerant-22.
The units are shipped in the vertical position ready for field installation.
They can be installed for horizontal operation by reversing the position
of the solid bottom panel with the return air duct flange on the front of
the unit.
ACCESSORIES—FIELD INSTALLED
SUPPLY AIR PLENUMS
These fully insulated plenums are available for free standing units
located within the conditioned space, are shipped knocked-down for
easy field assembly, are finished to match the exterior of the basic
unit, and have double deflection grills that can be adjusted to vary the
throw, spread and drop of the supply air.
RETURN AIR GRILLS
These expanded metal grills are available for free standing units
located within the conditioned space, are finished to match the exterior
of the basic unit and are shipped in one piece for easy installation.
BASES
Bases are available to raise vertical units above the floor. Outdoor air
may be introduced through these bases by cutting an access opening
to accommodate the outdoor air duct connection. These bases are fin-
ished to match the exterior of the basic unit. They may have to be insu-
lated in the field for certain applications.
THREE-PHASE ELECTRIC HEATERS
Electric heaters are available in several capacities to provide maxi-
mum flexibility. Both the air conditioning unit and the heater can be
selected to precisely match the cooling and heating requirements of
the conditioned space. These heaters are designed for easy field
installation over the supply air opening of the unit. They have been
tested by and will be shipped with a CSA label. Every heater will be
fully protected against excessive current and temperature by fuses
and two high limit thermostats.
Units with electric heat will require only one power supply for both the
heating elements and the supply air blower motor, and the power wir-
ing can be protected by either dual element/time delay fuses or an
inverse time circuit breaker.
Document Outline
- 1 unit suspension mounting (horizontal application) weights 5
- 2 keu operating weights (lbs.) 5
- 3 sound power ratings 6
- 4 heating capacity - electric heat accessory 7
- 5 steam coil capacity, mbh@2 psig 8
- 6 hot water capacity, mbh 8
- 7 pressure drop vs. gpm 8
- 8 capacity correction vs. gpm 8
- 9 supply air blower performance - KEU060 (5 TON) 9
- 10 supply air blower performance - KEU090 (7.5 TON) 10
- 11 supply air blower performance - KEU120 (10 TON) 11
- 12 supply air blower performance - KEU180 (15 TON) 12
- 13 static resistance for unit accessories (iwg) - KEU060-120 13
- 14 static resistance for unit accessories (iwg) - KEU180 13
- 15 supply air plenum performance data 14
- 16 BLOWER motor and drive data 14
- 17 KEU physical data 15
- 18 Unit Clearances keu060 16
- 19 Unit Clearances keu090 & 120 17
- 20 unit clearances keu180 18
- 21 ELECTRIC HEATER DIMENSIONS keu060, 090, 120 & 180 20
- 22 keu electrical data 22
- FIGURE 1 - vertical AND horizontal APPLICATION KEU060, 090 & 120
- FIGURE 2 - vertical and horizontal application keu180
- FIGURE 3 - suspension mounting (horizontal) - keu060, 090 and 120
- TABLE 1: unit suspension mounting (horizontal application) weights
- Table 2: keu operating weights (lbs.)
- FIGURE 4 - suspension accessory (horizontal) - KEU180
- Table 3: sound power ratings
- NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. Th...
- Table 4: heating capacity - electric heat accessory
- Table 5: steam coil capacity, mbh@2 psig
- Table 6: hot water capacity, mbh
- Table 7: pressure drop vs. gpm
- Table 8: capacity correction vs. gpm
- Table 9: supply air blower performance - KEU060 (5 TON)
- Table 10: supply air blower performance - KEU090 (7.5 TON)
- Table 11: supply air blower performance - KEU120 (10 TON)
- Table 12: supply air blower performance - KEU180 (15 TON)
- TABLE 13: static resistance for unit accessories (iwg) - KEU060-120
- TABLE 14: static resistance for unit accessories (iwg) - KEU180
- TABLE 15: supply air plenum performance data
- TABLE 16: BLOWER motor and drive data
- TABLE 17: KEU physical data
- Figure 1 - unit dimensions keu060
- TABLE 18: Unit Clearances keu060
- Figure 2 - unit dimensions keu090 & 120
- TABLE 19: Unit Clearances keu090 & 120
- Figure 3 - unit dimensions keu180
- Table 20: unit clearances keu180
- FIGURE 5 - accessory dimensionS
- TABLE 21: ELECTRIC HEATER DIMENSIONS keu060, 090, 120 & 180
- FIGURE 6 - RETURN AIR grill
- FIGURE 7 - Base Accessory
- FIGURE 8 - steam coil
- FIGURE 9 - hot water coil
- TABLE 22: keu electrical data
- TABLE 22: keu electrical data (continued)
- FIGURE 10 - field wiring for power supply
- FIGURE 11 - cooling only unit
- FIGURE 12 - unit with steam or hot water coil accessory
- FIGURE 13 - field wiring for units with electric heat