York PREDATOR DM 078 User Manual
Technical guide
246645-YTG-C-0708
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
STANDARD EFFICIENCY
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
DM 078, 090, 102, 120 and 150
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS
9.0 EER
TECHNICAL
GUIDE
®
®
DESCRIPTION
YORK
®
Predator
®
units are convertible single packages
with a common footprint cabinet and common roof curb for
all 6-1/2 through 12-1/2 ton models. All units have two
compressors with independent refrigeration circuits to pro-
vide two stages of cooling. The units were designed for
commercial applications and can be easily installed on a
roof curb, slab, or frame.
All Predator
®
units are self-contained and assembled on
rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide
a quick and easy field installation.
All units are convertible between side and down airflow. A
independent economizer design is used on side and down
discharge applications, as well as all tonnage sizes.
Predator
®
units are available in the following configura-
tions: cooling only, cooling with electric heat, and cooling
with gas heat. Electric heaters are available as factory-
installed options or field-installed accessories.
Tested in accordance with:
Document Outline
- DESCRIPTION
- TABLE OF CONTENTS
- LIST OF FIGURES
- 1 Predator® componeNt location 3
- 2 Unit 4 Point Load 35
- 3 Unit Center of Gravity 35
- 4 Unit 6 Point Load 35
- 5 Unit Dimensions 36
- 6 pREDATOR® Roof Curb dimensions 37
- 7 sUNLINE™ TO pREDATOR® tRANSITION roof curbs 38
- 8 BOTTOM DUCT OPENINGS (From above) 38
- 9 Rear Duct Dimensions 39
- 10 Downflow economizer hood detail 39
- 11 factory installed Downflow economizer 40
- 12 FIELD INSTALLED Downflow economizer W/POWER EXHAUST 40
- 13 FIELD INSTALLED HORIZONTAL economizer W/POWER EXHAUST 41
- 14 sLAB economizer dOWNFLOW W/POWER EXHAUST 41
- 15 SLAB economizer END RETURN W/POWER EXHAUST 42
- 16 cooling unit with gas heat wiring 230 volt diagram 43
- 17 cooling unit with/without electric heat wiring diagram 44
- 18 cooling unit with gas heat wiring 460, 575 volt and 50 hz diagram 45
- LIST OF TABLES
- 1 ACCESSORIES 8
- 2 DM PHYSICAL DATA 11
- 3 dm CAPACITY RATINGS 12
- 4 UNIT VOLTAGE LIMITATIONS 12
- 5 COOLING CAPACITY dm078 (6-1/2 TON) UNIT 13
- 6 COOLING CAPACITY dm090 (7-1/2 TON) UNIT 14
- 7 COOLING CAPACITY dm102 (8-1/2 TON) UNIT 15
- 8 COOLING CAPACITY dm120 (10 TON) UNIT 16
- 9 COOLING CAPACITY dm150 (12-1/2 TON) UNIT 17
- 10 electrical data dM078 (6-1/2 ton) std efficiency W/o PWRD CONVENIENCE OUTLET 18
- 11 electrical data dM078 (6-1/2 ton) std efficiency WITH PWRD CONVENIENCE OUTLET 18
- 12 ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/O PWRd CONV. OUTLET 19
- 13 ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/PWRd CONV. OUTLET 19
- 14 electrical data dM102 (8-1/2 ton) std efficiency W/o PWRD CONVENIENCE OUTLET 20
- 15 electrical data dM102 (8-1/2 ton) std efficiency WITH PWRD CONVENIENCE OUTLET 20
- 16 electrical data dM120 (10 ton) std efficiency W/ o PWRD CONVENIENCE OUTLET 21
- 17 electrical data dM120 (10 ton) std efficiency WITH PWRD CONVENIENCE OUTLET 21
- 18 electrical data dM150 (12-1/2 ton) std efficiency W/o PWRD CONVENIENCE OUTLET 22
- 19 electrical data dM150 (12-1/2 ton) std efficiency W/PWRD CONVENIENCE OUTLET 22
- 20 ELECTRIC HEAT Multipliers 22
- 21 dm078 (6-1/2 TON) SIDE SHOT BLOWER PERFORMANCE 23
- 22 DM090 (7-1/2 TON) SIDE SHOT BLOWER PERFORMANCE 24
- 23 DM102 (8-1/2 TON) SIDE SHOT BLOWER PERFORMANCE 25
- 24 dm120 (10 TON) SIDE SHOT BLOWER PERFORMANCE 26
- 25 dm150 (12-1/2 TON) SIDE SHOT BLOWER PERFORMANCE 27
- 26 dm078 (6-1/2 TON) DOWN SHOT BLOWER PERFORMANCE 28
- 27 DM090 (7-1/2 TON) down SHOT BLOWER PERFORMANCE 29
- 28 DM102 (8-1/2 TON) down SHOT BLOWER PERFORMANCE 30
- 29 DM120 (10 TON) DOWN SHOT BLOWER PERFORMANCE 31
- 30 dm150 (12-1/2 TON) DOWN SHOT BLOWER PERFORMANCE 32
- 31 Additional static resistance dm078, 120 and 150 33
- 32 Additional static resistance dm090, 102 33
- 33 electric heat MINIMUM SUPPLY AIR CFM 34
- 34 INDOOR BLOWER SPECIFICATIONS 34
- 35 POWER EXHAUST SPECIFICATIONS 34
- 36 4 Point Load Weight 35
- 37 6 Point Load Weight 36
- 38 Unit Weight 36
- 39 UNIT HEIGHT 36
- 40 Unit Clearances 36
- 41 Economizer Usage 40
- FIGURE 1 - Predator® componeNt location (DM 120 SHOWN)
- FEATURES
- FACTORY INSTALLED OPTIONS
- FIELD INSTALLED ACCESSORIES
- 1. Compressor Lockout (CLO): To prevent mechanical (compressorized) operation of the unit during cold outdoor conditions where there is a risk of returning liquid refrigerant back to the compressors.
- 2. Low Limit Control (LLC): To prevent the supply air from dropping below a specified setpoint by utilizing the units first stage heating means when there is a demand for cooling during cold outside conditions.
- NOMENCLATURE
- TABLE 2: DM PHYSICAL DATA
- TABLE 3: dm CAPACITY RATINGS
- TABLE 4: UNIT VOLTAGE LIMITATIONS
- TABLE 5: COOLING CAPACITY dm078 (6-1/2 TON) UNIT
- TABLE 8: COOLING CAPACITY dm120 (10 TON) UNIT
- TABLE 9: COOLING CAPACITY dm150 (12-1/2 TON) UNIT
- TABLE 12: ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/O PWRd CONV. OUTLET
- TABLE 13: ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/PWRd CONV. OUTLET
- TABLE 14: electrical data dM102 (8-1/2 ton) std efficiency W/o PWRD CONVENIENCE OUTLET
- TABLE 15: electrical data dM102 (8-1/2 ton) std efficiency WITH PWRD CONVENIENCE OUTLET
- TABLE 16: electrical data dM120 (10 ton) std efficiency W/o PWRD CONVENIENCE OUTLET
- TABLE 17: electrical data dM120 (10 ton) std efficiency WITH PWRD CONVENIENCE OUTLET
- TABLE 18: electrical data dM150 (12-1/2 ton) std efficiency W/o PWRD CONVENIENCE OUTLET
- TABLE 19: electrical data dM150 (12-1/2 ton) std efficiency W/PWRD CONVENIENCE OUTLET
- TABLE 20: ELECTRIC HEAT Multipliers
- TABLE 21: dm078 (6-1/2 TON) SIDE SHOT BLOWER PERFORMANCE
- TABLE 22: DM090 (7-1/2 TON) SIDE SHOT BLOWER PERFORMANCE
- TABLE 23: DM102 (8-1/2 TON) SIDE SHOT BLOWER PERFORMANCE
- TABLE 24: dm120 (10 TON) SIDE SHOT BLOWER PERFORMANCE
- TABLE 25: dm150 (12-1/2 TON) SIDE SHOT BLOWER PERFORMANCE
- TABLE 26: dm078 (6-1/2 TON) DOWN SHOT BLOWER PERFORMANCE
- TABLE 27: DM090 (7-1/2 TON) down SHOT BLOWER PERFORMANCE
- TABLE 28: DM102 (8-1/2 TON) down SHOT BLOWER PERFORMANCE
- TABLE 29: DM120 (10 TON) DOWN SHOT BLOWER PERFORMANCE
- TABLE 30: dm150 (12-1/2 TON) DOWN SHOT BLOWER PERFORMANCE
- TABLE 31: Additional static resistance dm078, 120 and 150
- TABLE 32: Additional static resistance dm090, 102
- TABLE 33: electric heat MINIMUM SUPPLY AIR CFM
- TABLE 34: INDOOR BLOWER SPECIFICATIONS
- TABLE 36: 4 Point Load Weight
- TABLE 37: 6 Point Load Weight
- TABLE 38: Unit Weight
- TABLE 40: Unit Clearances
- FIGURE 6 - pREDATOR® Roof Curb dimensions
- FIGURE 7 - sUNLINE™ TO pREDATOR® tRANSITION roof curbs
- FIGURE 8 - BOTTOM DUCT OPENINGS (From above)
- FIGURE 9 - Rear Duct Dimensions
- FIGURE 10 - Downflow economizer hood detail
- TABLE 41: Economizer Usage
- FIGURE 11 - factory installed Downflow economizer
- FIGURE 12 - FIELD INSTALLED Downflow economizer W/POWER EXHAUST
- FIGURE 13 - FIELD INSTALLED HORIZONTAL economizer W/POWER EXHAUST
- FIGURE 14 - sLAB economizer dOWNFLOW W/POWER EXHAUST
- FIGURE 15 - SLAB economizer END RETURN W/POWER EXHAUST
- FIGURE 16 - cooling unit with gas heat wiring 230 volt diagram
- FIGURE 17 - cooling unit with/without electric heat wiring diagram
- FIGURE 18 - cooling unit with gas heat wiring 460, 575 volt and 50 hz diagram
- GUIDE SPECIFICATIONS
- GENERAL
- DESCRIPTION
- REFRIGERANT COMPONENTS
- UNIT OPERATING CHARACTERISTICS
- 1. ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER – Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring- return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% ...
- 2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are f...
- ADDITIONAL FACTORY INSTALLED OPTIONS
- OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE