beautypg.com

Combustion vent – York ECO2 YPAL 050 User Manual

Page 46

background image

46

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

Installation

6. The furnace and its individual manual shut-off

valve must be disconnected from the gas supply
piping system during any pressure testing of that
system at test pressures in excess of 0.5 PSIG.

Disconnect gas piping from unit when
leak testing at pressures greater than
0.5 PSIG. Pressures greater than 0.5
PSIG will cause gas valve damage
resulting in a hazardous condition.
If gas valve is subjected to pressure
greater than 0.5 PSIG, it must be
replaced.

7. A 1/8 inch N.P.T plugged tapping, accessible for

test gage connection, must be installed immedi-
ately upstream of the gas supply connection to the
furnace.

COMBUSTION VENT

The combustion vent assembly is shipped in the return
air section of the unit. The combustion vent assembly
must be mounted over the fl ue gas outlet fi xed panel
located to the right of the gas heat access door. Install
as follows:

1. Remove the combustion vent assembly from the

return compartment.

2. Remove the vertical row of six screws on either

side of the fl ue gas outlet fi xed panel.

3. Mount the combustion vent assembly over the fl ue

gas outlets and attach to the gas outlet fi xed panel
using the screws removed in step 2.

4. See Figure 2-14 for the proper orientation of the

combustion vent. The internal baffl e(s) must direct
the fl ue gases upward.

FIG. 2-14 – COMBUSTION VENT

LD11766

This manual is related to the following products: