68

1600Xp Series installation and operation manual

BUILT-IN UPS FAULT PROTECTION FUNCTIONS (CONT’D)

Protection Item

Internal Overheat

DC Circuit

Overvoltage

DC Circuit

Overcurrent

lCd message

oVerHeAt

dC-oV

dC-oC

Cause

Fan failure;

High ambient temperature

Chopper malfunction

inverter/chopper fault

operation mode

After Fault

Shutdown – no output

bypass operation – Chopper and inverter are stopped

inverter ol – transfer to bypass

Audible Alarm

yes – Continuous buzzer

Visible Alarm

red Fault led on

relay Contact

Alarm

Fault relay closed

bypass relay closed

Auto-retransfer

no

Preventive Maintenance/Parts Replacement

Preventive Maintenance

toshiba 1600Xp Series of uninterruptible power systems have been designed to provide years of trouble-

free operation requiring a minimum of preventive maintenance.
the best preventive measure that the UpS user can take is to keep the area around the unit, particularly the

air inlet vents, clean and free of moisture and dust accumulations. if the atmosphere of the installation site

is very dusty, use a vacuum cleaner to periodically remove dust accumulations around and from the unit.

CAUTION

Only a qualified Toshiba representative should be allowed to perform any

routine maintenance or service on this equipment other than those preventive

maintenance details which are described directly above this caution.

Cleaning the Touchscreen

The touchscreen display is covered with a protective Teflon coating. It should be cleaned with a clean,

damp cotton cloth to avoid scratching the coating.