1600Xp Series installation and operation manual
Status Indicators
the four top and three bottom UpS status indicators on the main screen and their meanings are listed in
the table below. .
Indicator
Functional Description
96%
Shows the current load percentage.
100% / 11’
100% / 9’ 35”
100% / n/A
battery information: in on-line and battery back-up mode the display alternates between
battery charge percentage and estimated remaining battery runtime in:
minutes for runtimes > 10 min.
minutes and Seconds for runtimes < 10 min.
in other modes, the display alternates between battery charge percentage and “n/A.”
inV
Shows current UpS Status. indicator will change as the UpS status changes. For a
detailed listing see page 56.
12:35 pm
System time
dVCoH
Fault description Code - For a detailed listing see 53.
ASyn
warning description Code - For a detailed listing see page 54.
on-line
Current operating mode of the UpS - For a detailed listing see page 56.
Light Emitting Diodes (LED)
the following table describes the front panel led behaviors and the associated meaning.
LED
Behavior
Significance/Meaning
green - on
UpS is in on-line, backup, or battery test mode.
green - oFF
UpS in bypass mode.
green - oFF
UpS in shutdown mode.
red - on
one or more faults occurred. See Records: Faults for details.
red - Flashing
Charger overvoltage occurred.
red - oFF
no fault occurred.
Amber - on
Service Call needed,
Less than 6 mo. of Battery Life or Battery Life
End.
Amber - Flashing
one or more warnings occurred. See Records: Warnings for details.
Amber - oFF
no warning (normal, UpS in operation).
green - on
Input and Bypass voltage is within specified range.
green - Flashing
Input and Bypass voltage is over specified range.
green - oFF
Input and Bypass voltage is under specified range.
NOTE: On-Line/Fault LEDs - Appear Orange if Green and Red flash concurrently.
AC input
warning
on-line/
Fault