Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual
Page 72

64
1600Xp Series installation and operation manual
bypUV
bypass Undervoltage – bypass
voltage less than UPS specifica-
tions.
depends on UpS mode.
CAll
Service Call required – inspection
of the unit is advised.
Have inspection/service performed.
CHrgoV Charger overvoltage – battery
Charger not within specifications.
Contact the nearest toshiba authorized representa-
tive for service.
Clmt
Current limit – UpS not within
specifications.
Contact the nearest toshiba authorized representa-
tive for service.
dCer
display Cable error – display
cable is disconnected.
Connect the display cable.
ddCn
Communication error between
display and main Controllers.
Contact the nearest toshiba authorized representa-
tive for service.
Fbyper
bypass Frequency error – input
frequency outside of UPS specifi-
cations.
depends on UpS mode.
Fier
input Frequency error – input fre-
quency outside of 45-65 Hz range.
depends on UpS mode.
lb
low battery – the battery level
has dropped low (about 90% or
less) during operation. Continued
operation in this mode will deplete
battery and cause output shut
down.
immediately shut down the load equipment in an
orderly fashion and then press the Stop key.
ol110
overload – UpS is overloaded
(110% and above) Unit will switch
to bypass operation or shut down
if no action is taken.
Shut down excess equipment to reduce load.
rCer
Communication error between
remoteeye and UpS.
ensure remoteye is connected to UpS. Contact the
nearest toshiba authorized representative for service.
rSer
Communication error at Service
port.
Contact the nearest toshiba authorized representa-
tive for service.
rUer
Communication error at lAn.
Contact the nearest toshiba authorized representa-
tive for service.
VdCUVbt dC bus Undervoltage during bat-
tery test.
Contact the nearest toshiba authorized representa-
tive for service.
VioV
input overvoltage – input voltage
exceeds UPS specifications.
depends on UpS mode.
ViUV
input Undervoltage – input voltage
less than UPS specifications.
depends on UpS mode.