Communication Interfaces

Remote Contacts

the remote contacts interface is provided as a set of solid state switching devices. the switches are

available through a db9 male connector on the rear of the UpS. the following chart shows the pin

assignment for each signal.

MAxIMUM CURRENT CARRYING CAPACITY

OF THE SWITCH

DB9 MALE CONNECTOR OUTLINE

(FACING CONNECTOR)

Voltage

Current

48 Vdc peak

70 mA peak

30 Vac rms

(42 Vac peak)

50 mA rms

(70 mA peak)

Pin

Signal Function

Logic

In the UPS

1

Fault Signal

Closed when fault detected

2

UpS stop common

backup stop when the level

changes from low (-3 to -15 V) to

High (+3 to +15 V)

3

UpS stop signal input

4

normal input power supply

Closed with normal supply power

5

Signal common

Common signal return

6

bypass operation

Closed during bypass operation

7

battery voltage drop

Closed at voltage drop

8

UpS operation

Closed during inverter operation

9

power failure signal

Closed at power failure

NOTE: pin switches are shown in their inactive states. For example, if battery voltage is low, pin 7 will be connected to pin 5.