Battery Backup Time and Discharge Process

the UpS batteries provide approximately 5-7 minutes of back-up time depending on the 1600Xp unit kVA

rating. these times are valid when the unit is operating under full load and at the rated power factor. the

exact length of these times will depend on the UpS model used, condition of the batteries, amount and

type of load, temperature and other variables. See battery backup time in ‘UPS Specifications’ beginning

on

page

19.

the following illustration graphically shows the battery discharge process at full load conditions.

Battery Low Voltage Tolerances

excessive discharge will cause the UpS battery voltage to drop. the chart shown below lists the voltage

level at which each UpS low-voltage alarm will sound and at what level the low-voltage condition will

cause the unit to automatically shut down.

UPS Capacity

3.6 kVA

6 kVA

8 kVA

10 kVA 14 kVA 18 kVA

22 kVA

nominal voltage (Vnom)

144 Vdc 216 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc

Alarm voltage (Vlow)

130 Vdc 192 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc

Shutdown voltage (Vmin)

114 Vdc 170 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc

BATTERY CAPACITY

SHUTDOWN

I

MAx

I

MIN

V

NOM

V

LOW

V

MIN

100%

20% 0%

CURRENT VOLTAGE