Starting/stopping the ups, Notice – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual

Page 35

background image

27

1600Xp Series installation and operation manual

Starting/Stopping the UPS

turn the main circuit breaker (mCCb) on the back of the UpS (see

pages

65-66) to the

ON position. the

breaker should normally remain in the

ON position.

Verify that the

On-Line led on the front panel (see

page

32) lights green. All led’s on the front panel may

light for a moment when the input breaker is turned on. this is normal. the UpS will now be supplying

power in the bypass mode.

NOTICE

When running the UPS for the first time or after the power failure backup

operation, charge the batteries for at least 24 hours (input breaker on) before

operating the connected load.
Using the UpS without charging the battery shortens the battery backup operation

time, which may result in the destruction of data in case of a power failure.

press

RUN key to begin UpS operation (see page 37 for startup screens).

NOTICE

If the input breaker is turned off while UPS is in the bypass state, the output

power stops. Any load devices will lose power.
ensure that all sensitive loads have been previously shut down.

Stopping the UPS

to stop the UpS press and hold the

STOP key approximately 1 second until the On-Line led changes

from green to off. the UpS is now in the bypass mode.

to completely stop the UpS, turn the input breaker at the back of the UpS to the

OFF position.