Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual
Page 28
20
1600Xp Series installation and operation manual
STANDARD MODELS: 3.6 – 10 KVA (CONT’D)
Unit (Capacity)
3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
environment
operating temperature
59 – 77 °F (15 – 25 °C)
recommended
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
Storage temperature
-4 – 104 °F (-20 – 40 °C)
installation Area
to be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
operating Humidity
30 – 90% non-condensing
Altitude
< 6600 ft. (2000 m) above sea level
2
Acoustical noise
50 db (A) maximum @ 1 meter from front panel
Heat generation (typical)
2139 btU/Hr
3564 btU/Hr
4095 btU/Hr
5118 btU/Hr
operation diagnosis
battery Check
Performed on start up, by schedule, on-demand (user configurable)
input oV protection
Standard
battery lifetime
UpS calculates battery replacement time
based upon battery ambient temperature (lCd display, led and beeps)
internal temperature
UpS gives indication of internal temperature, alarm when high temp
event data Storage
32 – operation, 32 – backup, 32 - warnings, 32 – Faults, 32 - test, 32 - System
Applications
Switches
generator compatible
bypass Switch
bypass disable
Static switch < ¼ cycle (50 Hz – 5 ms/60 Hz – 4.16 ms)
Automatic retransfer
Factory or authorized service center selectable only
interface/Communications
real time Clock
real time Clock with backup lithium ion battery
Schedule operation
Schedule on/oFF operation of UpS using optional remtoeye iii communication software
Autostart
Automatic UpS Startup when AC is applied - option can be enabled or disabled at user’s
discretion
remote on/oFF
Standard – external terminal
emergency power off
Standard – terminal contacts only
led display
3 led’s indicating on-line/Fault, warning, and A/C input
operator interface
interactive touchscreen
buzzer Volume
Standard (Fixed Volume)
power Connections
Standard – Hard wire, optional – receptacle panel w/ power Cord
remote Contacts
Standard (inV, byp, bAtt, lb, AC, Flt)
rS232 ASCii interface
toshiba UpS Communication protocol 2.0
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid
1.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%
2.