Battery recharging – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual

Page 36

background image

28

1600Xp Series installation and operation manual

Battery Recharging

the illustration below shows a graphical representation of the UpS battery recharge process after a full

discharge.

The recharge process usually consists of three periods. During the first period, the current is maintained

at approximately 1 ampere. this current limit is the maximum value that can be used to charge the

batteries (for minimal recharge time) while assuring safety and long battery life. in the second period,

constant-voltage control starts and current gradually decreases as the batteries charge to their normal

fully charged state. In the third period, a slight trickle current continues to flow into the batteries to keep

them fully charged and floating at the normal Vdc level. A full recharge usually requires 24 hours (90%

recharge in 12 hours) after a complete discharge.

the following chart shows the rated maximum and minimum battery voltages and the charge current for

each of the sizes.

RATED BATTERY VOLTAGES

Model

Vmax

Vmin

Icharge

3.6 kVA

163 V

114 V

1.0 A

6 kVA

245.7 V

170 V

1.0 A

8 kVA

327 V

227 V

1.0 A

10 kVA

327 V

227 V

1.0 A

14 kVA

327 V

227 V

1.0 A

18 kVA

327 V

227 V

1.0 A

22 kVA

327 V

227 V

1.0 A

BATTERY

CHARGE

VOLTAGE

CURRENT VOLTAGE

CHARGING

CURRENT

I

CHARGE

V

MAx

V

MIN

DISCHARGE

SHUT-OFF

POINT

PERIOD 1

PERIOD 2

PERIOD 3

TIME

FULLY

CHARGED

0

0