System Fault Messages

A Fault message is generated when either a fault condition occurs, or a warning condition occurs three

times within ten minutes. the table below shows the possible fault messages and what actions need be

taken.

if the input voltage is normal when the fault occurs then the UpS will switch immediately to the bypass mode

to continuously feed power to the load.

if the fault condition occurs while the input power is abnormal and the UpS is in bypass mode the UpS will

shut down the output to prevent load equipment damage.

when a Fault condition exists, the red led on the UpS display panel will illuminate until the fault is

cleared.

Display

Meaning

Action

bypoH

bypass overheat – overheating

condition occurred.

Check unit for blocked or in-operable fan. lower am-

bient temperature if it is greater than 104 °F (40 °C).

bypass operation will also cease if overheat condition

is not corrected within 1 hr. of inverter shutdown. try

restarting. if condition re-occurs plan for total shut-

down and call for service.

bypol

bypass overload – UpS is over-

loaded.

Shut down excess equipment to reduce load.

CHrgoV Charger overvoltage – Charger

overvoltage condition occurred.

UpS is possibly faulty. Check the UpS operation

conditions at time of fault. not advisable to restart the

UpS. Call for service.

Clmt

Current limit – load on UpS out-

put exceeds unit specifications.

reduce load on UpS output.

dCib

dC bus imbalance – dC voltage

imbalance occurred.

possible causes are UpS fault are connection of half-

wave rectifier load. Check load and try restarting. If

condition persists, call for service.

dCoC

dC bus overcurrent – dC overcur-

rent condition occurred.

UpS is possibly faulty. Check the UpS operation

conditions at time of fault. not advisable to restart the

UpS. Call for service.

dCoV

dC bus overvoltage – dC over-

voltage condition occurred.

UpS is possible faulty, input wiring error, input over-

voltage or connection of a motor load. try restarting. if

condition persists call for service.

dCUVbS

dC bus Undervoltage during

boostup mode – dC bus under-

voltage condition occurred.

UpS is possibly faulty. Check the UpS operation

conditions at time of fault. not advisable to restart the

UpS. Call for service.

dCUVC

dC bus Undervoltage during

Charging mode – dC bus under-

voltage condition occurred.

UpS is possibly faulty. Check the UpS operation

conditions at time of fault. not advisable to restart the

UpS. Call for service.

dVCoH

device overheat – overheating

condition occurred.

reduce equipment load to 100% or less and try

restarting.

FSopen

Fuse open.

replace fuse.

inVolnr inverter overload (not reset-

table) – output overload condition

occurred.

reduce equipment load to 100% or less and manually

restart the UpS.