Important safety instructions, Qualified personnel only – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual
Page 11
3
1600Xp Series installation and operation manual
IMPORTANT SAFETY INSTRUCTIONS
this manual contains important instructions that should be followed during the installation and maintenance
of the UpS and its batteries.
Hardwired UpS units are not equipped with an over-current protection device nor an output disconnect for
the AC output. A circuit breaker should be provided by the user between the UpS output and the load input.
this device should be rated as follows:
240VAC
RATING
3.6 kVA
6 kVA
8 kVA
10 kVA
14 kVA
18 kVA
22 kVA
20 A
35 A
45 A
60 A
80 A
100 A
125 A
the nominal battery voltages for these models are as follows:
BATTERY
VOLTAGE
3.6 kVA
6 kVA
8 kVA
10 kVA
14 kVA
18 kVA
22 kVA
144 Vdc
216 Vdc
288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc
Servicing of the batteries should only be performed by a qualified factory authorized representative who
is knowledgeable about batteries and the required precautions. keep unauthorized personnel away from
batteries. to arrange for battery replacement, contact your nearest factory authorized service center.
turn off, lockout, and tagout all equipment before connecting the power wiring to the equipment or
1.
when performing maintenance.
Hardwired UpS units are not equipped with an over-current protection device, nor do they have an
2.
output disconnect for the AC output. therefore, a user-installed circuit breaker should be provided
between the UpS output and the load input.
the
3.
maximum ambient operating temperature is 104 °F (40 °C).
Access panels should only be removed by authorized Toshiba field Service personnel.
4.
UPS servicing should be performed by qualified Toshiba representatives only.
5.
Battery servicing should be performed by qualified Toshiba representatives only.
6.
Contact your toshiba authorized service center for battery replacement.
7.
QUALIFIED PERSONNEL ONLY
Qualified personnel are those who have the skills and knowledge relating to the construction, installation,
operation, and maintenance of the electrical equipment and have received safety training on the hazards
involved (refer to the latest edition of nFpA 70e for additional safety requirements).
Qualified personnel shall:
Have read the entire operation manual.
1.
be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and
2.
equipment, and clear faults in accordance with established safety practices.
be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard
3.
hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices.
Be trained in rendering first aid.
4.
be knowledgeable about batteries and their required handling and maintenance precautions.
5.
For further information about workplace safety visit www.osha.gov.