Ups specifications – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual
Page 27
19
1600Xp Series installation and operation manual
UPS Specifications
STANDARD MODEL: 3.6 – 10 KVA
Unit (Capacity)
3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
general
topology
true on-line
Certifications
AnSi C62.41 (ieee 587), Ul 1778, CUl, Ce, FCC Class A , neC (nFpS-70), nemA/
pe1-1993, oSHA, ASme, iSo 9001, iSo 14001:2004 , roHS Compliant
input Characteristics
input Voltage
1
Single-phase, 208/240 Vac, +10% to -30%
1
input Frequency
45 – 65 Hz (auto-sensing)
input Capacity
3.6 kVA
6 kVA
8.0 kVA
10 kVA
input /(max input) Current @208V
17.9 (18.7) A
29.8 (31.1) A
38.9 (40.5) A
48.6 (50.2) A
input/(max. input) Current @240V
15.5 (16.2) A
25.9 (27.0) A
33.7 (35.1) A
42.1 (43.5) A
input power Factor
0.98 typical, 0.95 minimum@ 100% load
Current tHd (linear load)
< 5% total harmonic distortion
internal AC input breaker rating
30 A/277 V
50 A/277 V
60 A/277 V
63 A/277 V
battery Characteristics
battery type
Valve regulated lead Acid, Flame retardant
backup time, fully charged @ 0.7
power factor, 77 °F
8 min.
2
8 min.
2
7 min.
2
7 min.
2
backup time, fully charged @ 0.85
power factor, 77 °F
7 min.
2
7 min.
2
7 min.
2
5 min.
2
recharge time
24 hr. (full), 12 hr. (90%) for internal batteries only
3
battery Voltage (nominal)
144 Vdc
216 Vdc
288 Vdc
output Characteristics
output Voltage
Single-phase, 240/208/120 V
output Voltage regulation
= ± 3%
output Frequency
±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)
AUto/mAn Frequency
Factory or authorized service center selectable only
Voltage tHd
< 3% for linear load; < 6% for non-linear load
Common-mode noise
< 0.5 Vrms
rated load power Factor
1
0.85 (0.6 – 1.0) lagging
Efficiency (ac-dc-ac)
>83%
>85%
Voltage transient
< ±8% (load of 0 – 100 %)
Voltage transient recovery
50 ms to within 2% of nominal
rated output Current (rms)
15 A
25 A
33.3 A
41.6 A
max peak output Current
45 A
75 A
100 A
125 A
inverter overload Capacity
125% for 30 sec./150% for 10 sec.
bypass overload Capacity
125% for 10 min./1000% for 1 cycle
Crest Factor
3.0
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid
1.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
battery
2.
backup time may vary depending on the operating conditions and ambient temperature at the installation site.
An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
3.