1600Xp Series installation and operation manual

STANDARD MODELS: 14 – 22 KVA (CONT’D)

Capacity

14 kVA (11.9 kW)

1

18 kVA (15.3 kW)

1

22 kVA (18.7 kW)

1, 4

environment
operating temperature

59 – 77 °F (15 – 25 °C)

recommended

60 Hz 32 – 104 °F (0 – 40 °C)

50 Hz 32 – 91 °F (0 – 33 °C)

Storage temperature

-4 – 104 °F (-20 – 40 °C)

installation Area

to be installed in a well ventilated area free of airborne dust,

metal particles or flammable gas, allow at least 4 inches on all sides

operating Humidity

30 – 90% (no condensation)

Altitude

< 6600 ft. (2000 m) above sea level

2

Acoustical noise

50 db (A) maximum @ 1 meter from front panel

Heat generation (typical)

6610 btU/Hr

3

8499 btU/Hr

3

10,387 btU/Hr

3

operation diagnosis
battery Check

Performed on start up, by schedule, on-demand (user configurable)

input oV protection

Standard

battery lifetime

UpS calculates battery replacement time based upon

battery ambient temperature (lCd display, led and beeps)

internal temperature

UpS gives indication of internal temperature, alarm when high temp

event data Storage

32 – operation, 32 – backup, 32 - warnings, 32 – Faults, 32 - test,

32 - System

Applications
Switches

generator compatible

bypass Switch
bypass disable

Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms)

Automatic retransfer

Factory or authorized service center selectable only

interface/Communications
real time clock

real time Clock with backup lithium ion battery

Schedule operation

Schedule on/oFF operation of UpS using optional remoteye iii communication

software

Autostart

Automatic UpS Startup when AC is applied - option can be enabled or disabled at

user’s discretion

remote on/oFF

Standard – external terminal

led display

3 led’s indicating on-line/Fault, warning, and A/C input

operator interface

interactive touchscreen

buzzer Volume

Standard (Fixed Volume)

power Connections

Standard – Hard wire

emergency power off

Standard – terminal contacts only

remote Contacts

Standard (inV, byp, bAtt, lb, AC, Flt)

rS232 ASCii interface

toshiba UpS Communication protocol 2.0

Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid

1.

when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.

At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%

2.

Subject to update without notice.

3.

derate to 18.7 kVA (15.9 kw) for 50 Hz operation.

4.