1600Xp Series installation and operation manual

UPS Protection System

System Protection Features

the following schematic shows the electrical locations of the protection devices on the UpS.

System Protection Functions

the following charts show the built-in system fault protection functions on all the UpS models.

BUILT-IN UPS FAULT PROTECTION FUNCTIONS

Protection Item

Output Overvoltage Output Undervoltage

Output Overload

lCd message

OUT-OV

OUT-UV

OVERLOAD

Cause

Control malfunction;

chip error

Control malfunction;

Fuse opened; load issue overload – Short circuit at load

operation mode

After Fault

bypass operation – Chopper and inverter are

stopped

inverter ol: transfer to bypass;

bypass ol: inverter, chopper

stopped

Audible Alarm

yes – Continuous buzzer

See Audible Alarm Functions on

page 31

Visible Alarm

red Fault led on

inverter ol: Fault lamp off

bypass ol: Fault lamp on

relay Contact

Alarm

Fault relay closed

bypass relay closed

Fault relay open;

inverter ol: bypass relay closed

bypass ol: bypass relay open

Auto-retransfer

no

inverter ol: yes if bypass is ok

bypass ol: no

input

Abnormal

low battery

level

overheating

overcurrent

Current limit

overload

overvoltage/

Undervoltage

Output

Power

Line Filter

Inverter

*Static Switch

Isolation

Transformer

Input

Power

Input

Fuse

Power Flow

Bypass

* Switches are

solid state

devices.

MCCB

Output

Fuse

Surge

Absorber

Batteries

+

Rectifier/

Chopper

Negative

Bus