beautypg.com

Operating the ups, Initial startup (first power-up) – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual

Page 33

background image

25

1600Xp Series installation and operation manual

Operating the UPS

the 1600Xp should be installed and adjusted by an operator. once installed, the 1600Xp is designed

to be operated by laymen. Anyone not familiar with this UpS should read the manual before attempting

to operate it.

Initial Startup (First Power-Up)

The first time the UPS is activated after being shipped from the factory, an initialization program will

require the operator to input the following parameters. input rated Voltage, output rated Voltage, UpS

date, and UpS time. the UpS display operation is explained in detail on pages 32-59.
the input frequency defaults to 60 Hz.
The first screen displayed during the initial startup sequence requires the operator to select the nominal

input Voltage. Select from 208V, 230V, or 240V, and press the

Write key.

if the command has been accepted, the word “Successful” will appear at the bottom left side of the

display.
repeat the process in step 1 in selecting the rated output Voltage.

1.

Use the keypad to type in the current date in the format:

2.

Mon 10/05/2009. and press

Write.

Use the keypad to type in the current time in 12 hour format:

3.

12:15 PM and press

Write.

the main screen is now displayed. Verify the UpS is in bypASS mode. the mode (lower right side

4.

of the display) should display

Bypass. if it does not display Bypass, press and momentarily hold

the

STOP button on the main display.

with the UpS in bypass mode, cycle power to the UpS as follows:

5.

At the rear of the UpS switch the main circuit breaker mCCb to oFF.

leave the UpS off until the dC bus is safely discharged (approximately 5-10 minutes).

restart the UpS by switching the main circuit breaker on.

the table below summarizes the initialization parameters:

ID

Command

Options

111

rated Vin

Select from 208V, 230V, or 240V, and press

Write.

215

rated Vout

Select from 208V, 230V, or 240V, and press

Write.

634

UpS date

input the date in this format: Mon 10/05/2009. and press

Write.

635

UpS time

input the current time in 12 hour format: 12:15 PM and press

Write.