Ups connections, Terminal block – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual
Page 21
13
1600Xp Series installation and operation manual
UPS
Connections
Terminal Block
the following illustration is a detail view of the terminal block and wiring connections used for 208/240
volt units (see
pages
65-66 for terminal block location).
* – if only one input line is hot, connect hot line to terminal 1 (l), and connect the neutral line to terminal 2 (n).
note 1 – if AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. do not jumper terminal 13 to 12 or
11. Factory Setting is 208Vac.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
note 2 – if AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. do not jumper terminal 11 to 12 or
13.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
240V
208/240 V
in
REMOTE1
208
EPO2
EPO1
REMOTE2
COM 240
g
X3
1
l2 (n*)
g
X1
X2
n (0V)
2
3
12
14
13
15
8
7
6
5
11
4
16 17
l1 (l*)
120 V
240 V
120 V
208 V
208V
Jumper selection
See notes 1&2
inpUt
oUtpUt
- Power Inverter (15 pages)
- 1800 (6 pages)
- TOSVERT VF-S11 (68 pages)
- Uninterruptible Power System G9000 (104 pages)
- Density (Consistency) Meter LQ500 (9 pages)
- MBSB80-225-43 (1 page)
- TOSNIC-7000S (53 pages)
- 1600EP Series (3 pages)
- 1500 (32 pages)
- TOSVERT VF-FS1 Series (16 pages)
- 4200FA XT1 (1 page)
- G3 Plus Pack (4 pages)
- Tosvert VF-A5 (149 pages)
- 1600 Series (3 pages)
- G9000 (100 pages)
- TEC EO1-33030 (54 pages)
- 1000 Series (2 pages)
- 1500 Plus (31 pages)
- G8000MM (6 pages)
- VT130G1 (99 pages)
- 4200FA Series (2 pages)
- VF-PS1 (10 pages)
- GX7 Series (6 pages)
- 4200FA XT (1 page)
- RMTI-EMD-HT (2 pages)
- W7 Series (6 pages)
- HX7 (6 pages)
- PDP002Z (18 pages)
- RELIABILITY IN MOTION 1700 (39 pages)
- 1700 Series (2 pages)
- G3 TOSVERT-130 (62 pages)
- B-852-TS12-QP (55 pages)
- 1000 (4 pages)
- E3 (7 pages)
- Adjustable Speed Drive H3 (122 pages)
- 55611-001 (2 pages)
- Black Gold Series (2 pages)
- Dura-Bull TX (6 pages)
- Current Relay RC803A-HP1 (19 pages)
- 1800 SERIES (2 pages)
- Isolated-Redundant UPS System (2 pages)
- Tosvert VF-AS1 (312 pages)
- RELIABILITY IN MOTION 1000 (54 pages)
- REMOTE-D (2 pages)
- 15-80KVA (2 pages)