Ups connections, Terminal block – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual

Page 21

background image

13

1600Xp Series installation and operation manual

UPS

Connections

Terminal Block

the following illustration is a detail view of the terminal block and wiring connections used for 208/240

volt units (see

pages

65-66 for terminal block location).

* – if only one input line is hot, connect hot line to terminal 1 (l), and connect the neutral line to terminal 2 (n).
note 1 – if AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. do not jumper terminal 13 to 12 or

11. Factory Setting is 208Vac.

Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.

note 2 – if AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. do not jumper terminal 11 to 12 or

13.

Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.

240V

208/240 V

in

REMOTE1

208

EPO2

EPO1

REMOTE2

COM 240

g

X3

1

l2 (n*)

g

X1

X2

n (0V)

2

3

12

14

13

15

8

7

6

5

11

4

16 17

l1 (l*)

120 V

240 V

120 V

208 V

208V

Jumper selection

See notes 1&2

inpUt

oUtpUt