Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual
Page 56
48
1600Xp Series installation and operation manual
1600
xP
Command Parameters T
able
Cmd
ID
Description
on LCD
Brief Description
Location Map
Example
Rqd Security Level to change
By
Tab
Block
101
Input Config
Input Configuration which tell the voltage and frequency
.
m
onitor
in
240V - 60Hz
n
onchangeable
n
onchangeable
User
Administrator
102
n
o of
input
line
n
o of
input
lines
- Always 1 input line for 1600X
p series
Setting
in
1
line
n
onchangeable
n
onchangeable
User
Administrator
103
input V
oltage
input V
oltage
- U
p
S presently calculated input voltage
m
onitor
in
240 V
n
onchangeable
n
onchangeable
User
Administrator
104
input Current
input Current
- U
p
S presently calculated input current
m
onitor
in
25.0
A
n
onchangeable
n
onchangeable
User
Administrator
105
input Fre
-
quency
input Frequency
- U
p
S presently calculated input frequency
m
onitor
in
60.0 Hz
n
onchangeable
n
onchangeable
User
Administrator
106
input
p
ower(
w
)
input
Active
p
ower
- U
p
S presently calculated input active power
.
if U
p
S can not calculate for input apparent
p
ower
, display shows
n
/A.
m
onitor
in
5100
w
n
onchangeable
n
onchangeable
User
Administrator
107
input p
ower(V
A)
input
Apparent
p
ower
- U
p
S presently calculated input apparent
power (input voltage * input current)
m
onitor
in
6000 V
A
n
onchangeable
n
onchangeable
User
Administrator
108
input
p
Factor
input
p
ower Factor
- i
f converter is not running, display shows
n
/A.
m
onitor
in
1.0
n
onchangeable
n
onchangeable
User
Administrator
111
r
ated V
in*
r
ated
input V
oltage
- Used to calculate percentage and required to setup properly at very first time startup.
Setting
in
240 V
n
onchangeable
Changeable
User
Administrator
112
r
ated
iin
r
ated
input Current
- Use this setup to calculated percentage.
m
onitor
in
25.0
A
n
onchangeable
n
onchangeable
User
Administrator
113
r
ated Fin
r
ated
input Frequency
- d
etected if auto detection and manual
m
onitor
in
60.0 Hz
n
onchangeable
n
onchangeable
User
Administrator
119
V
io
V
d
el
evel
input
o
vervoltage
d
etection
level
- Of rated input voltage which was configured with Command
id
1
11.
Setting
in
274 V
n
onchangeable
n
onchangeable
User
Administrator
120
V
io
V
r
el
evel
input
o
vervoltage
r
ecovery
level -
o
f rated
input voltage which was configured with Com
-
mand
id
1
11.
Setting
in
264 V
n
onchangeable
n
onchangeable
User
Administrator
135
input V
olt
-
age(%)
input V
oltage
p
ercentage
m
onitor
in
100 %
n
onchangeable
n
onchangeable
User
Administrator