Operating Modes

On-Line (Run operation)

The following illustration shows circuit power flow when the UPS is operating normally in the on-line

mode. The UPS rectifier, including a boost chopper circuit, converts AC input power to DC power. The

boost chopper circuit maintains a constant voltage, with current limiting, for charging the batteries. it also

supplies a dC voltage of the proper level to the inverter section. the inverter section generates a high

quality sinusoidal output voltage. the unit’s batteries are always maintained in a constantly charged state

when the UpS is in the run operation mode.

Static-Bypass (Stop operation)

If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched

from the unit’s main circuit to the bypass circuit. Power flow through the bypass is shown in the following

illustration. this change-over occurs automatically in phase in less than one-quarter cycle of the input

waveform. the switching period is not long enough to cause interruptions to occur in most loads.

If the power flow is transferred to the bypass circuit because of an overload and that overload condition

ends within a specified period of time then the power flow will be transferred back to the

On-Line

mode (run operation) automatically.
If the power flow is transferred to the bypass circuit due to an external

fault the UpS will shut down

power through the bypass to the load and indicate a system fault message.
If the power flow is transferred to the bypass circuit due to an internal fault the UPS will continue to

supply power to the load through the bypass and indicate a system fault message (see system fault

messages on

pages

53–54).

If the power flow is transferred to the bypass circuit due to an overload condition (see system warning

messages on

pages

54–55), then the power flow will automatically transfer from the UPS’s bypass

circuit back to the inverter circuit after removing the overload if set to do so (AutoreXfer parameter

(Cmd id 662)).

Output

Power

Line Filter

Inverter

*Static Switch

Isolation

Transformer

Input

Power

Input

Fuse

Power Flow

Bypass

* Switches are

solid state

devices.

MCCB

Output

Fuse

Surge

Absorber

Batteries

+

Rectifier/

Chopper

POWER FLOW IN ON-LINE MODE FOR ALL MODELS

Negative Bus

POWER FLOW IN BYPASS FOR ALL MODELS

Output

Power

Line Filter

Inverter

*Static Switch

Isolation

Transformer

Input

Power

Input

Fuse

Power Flow

Bypass

* Switches are

solid state

devices.

MCCB

Output

Fuse

Surge

Absorber

Batteries

+

Rectifier/

Chopper

Negative Bus