System mode messages, System status messages – Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual

Page 73

background image

65

1600Xp Series installation and operation manual

System Mode Messages

A UpS mode message is generated when the UpS changes operating mode. the following tables list the

possible operating modes for the UpS.

Display

Meaning

backup

backup – power comes from other than input.

batttest

battery test – battery test in progress.

bypass

Bypass – UPS is offline, power is being provided directly from UPS input.

on-line

on-line – input converter and inverter are running (double conversion mode).

Shutdown

Shutdown – no output, dC bus is charged through Softstart resistor.

Startup

Startup – UpS is starting up.

System Status Messages

A UpS Status message is generated when the UpS changes its status (from inverter to bypass mode, for

example). the table below shows the possible Status messages and their meaning.

Display

Meaning

Action

byp

bypass mode – power is supplied by UpS input.

no action needed.

CHrgerr

Charger error – Charger overvoltage error.

Contact the nearest toshiba autho-

rized representative for service.

dlySt

delay Start – UpS is counting down prior to

startup.

no action needed.

ee1St

eeprom is loaded with default values.

no action needed.

ee2rAerr eeprom to rAm loading error.

Contact the nearest toshiba autho-

rized representative for service.

eeUperr

eeprom updating error.

Contact the nearest toshiba autho-

rized representative for service.

epo

epo circuit is active.

reset epo switch to start.

FierrSt

Frequency input error Start – input frequency

could not be detected and UpS starts up with

default eeprom setup.

ensure correct input frequency is

selected in UpS settings.

Flt

A fault has occurred.

See Fault records.

FwUperr

Firmware Update error.

Contact the nearest toshiba autho-

rized representative for service.

init

initialization – UpS is inatilizing.

no action needed.

inV

inverter mode.

inverter is running (it can be on-

line, battery test, or backup)

lAnSd

UpS goes to Shutdown triggered from lAn Sd

circuit.

deactivate lAn shutdown signal to

reset.