beautypg.com

Library specifications, Library specifications 25, Table 1-8 – Sun Microsystems StreamLine SL8500 User Manual

Page 65

background image

Library Specifications

96154 • Revision K

Chapter 1 Introduction 25

Library Specifications

TABLE 1-8

Library Specifications

Physical

• Hmeight
• Width
• Depth (Base Library)

With 1 expansion module

With 2 expansion modules

With 3 expansion modules

2.37 m (236.6 cm) or 7.76 ft (93.15 in.)
1.7 m (170.8 cm) or 5.6 ft (67.25 in.)
2.8 m (276.9 cm) or 9.1 ft (109 in.)
3.7 m (372.1 cm) or 12.2 ft (146.5 in.)
4.7 m (467.4 cm) or 15.3 ft (184 in.)
5.6 m (562.6 cm) or 18.5 ft (221.5 in.)

• Weights

Base Library

With 1 expansion module

With 2 expansion modules

With 3 expansion modules

• Weight distribution per pad

Library only:

1954 kg (4,309 lb)
2392 kg (5,274 lb)
2830 kg (6,239 lb)
3396 kg (7,487 lb)

454 kg (1,000 lb)

• Pass-thru Port

Height

Width

Depth

Weight

231 cm (91 in.)
17.2 cm (6.76 in.)
150.8 cm (59.4 in.)
121 kg (266 lb) including the mechanisms

• Service Clearances

Customer Interface Module

Drive & Electronics Module

Pass-thru port (between)


66 cm (26 in.)
85 cm (33.5 in.)
15.24 cm (6 in.)

• Temperature

Operating

Shipping

Storing

+16 to +32°C (+60 to +90°F)
-30.5 to +49°C (-23 to +120°F)
+4.4 to +32°C (+40 to +90°F)
+25.6°C (+78°F) maximum, non-condensing

• Wet bulb (operating)

Humidity

Operating

Shipping

Storing

20% to 80%
5% to 90%
20% to 80%

• Operating Heat Output

44,380 Btu/hr (maximum loading**)
Calculation for this is: 3.41214 x Watts = Btu/hr

• Power Consumption
Single phase configuration and three phase
configurations

13.0 kW (maximum loading**)
13.7 kVA

kVA = kWatts ÷ Power factor
The power factor for the SL8500 = 0.95

**Maximum loading includes 64 tape drives, 4 fully loaded racks, 8 HandBots, all the front frame components
(CAPs, service door, and elevators), plus redundant control modules.