Figure 4-11 – Sun Microsystems StreamLine SL8500 User Manual

Page 109

background image

Powering-off the Library

96154 • Revision K

Chapter 4 Library Operation 69

4. Make sure that the drives are empty by verifying the drive state using the

StreamLine Library Console.

Note –

Refer to the online help documentation accessible through the Library Console

application.

5. Open the rear doors of the library.

6. Locate the power distribution unit (PDU) and move the system power-off/on switch

to the OFF position (0).

Note –

If the library has a 2N power configuration, you must switch off the system

power on both the PDUs.

An AC PDU is shown in

FIGURE 4-11

.

Figure 20

illustrates the locations of all power supplies (except for the Customer

Interface Module’s front frame area).

FIGURE 4-11

AC PDU

1. Retainer
2. LEDs
3. System Power Off/On Switch